Abstract

A time constant derived from a t-squared fire with the geometry of an atrium is proposed to specify the smoke filling time. The smoke filling pro cesses in 27 atria with volume varying from 2,500 to 35,000 m 3 were simulated by the fire zone model CFAST version 2.0. The atria are located adjacent to a "fire" shop at a lower level. Correlation relationships between the smoke filling time and the time constant are derived. Further, performance of smoke control systems in the atria are evaluated.
Source: crossref · Quality: baseline

Research context

OpenAlex topics: Fire dynamics and safety research · Evacuation and Crowd Dynamics · Flame retardant materials and properties

SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.

Affiliations

Department of Building Services Engineering The Hong Kong Polytechnic University Hung Hom, Kowloon, Hong Kong

References (11)

Show source-provided references
1. 1993
2. 10.1002/fam.81017020410.1002/fam.810170204 ↗
3. 10.1002/fam.81018050810.1002/fam.810180508 ↗
4. Chow, W.K. 1995. "Fire Aspects for Atrium Building in Hong Kong," in Proceedings of the 7th International Research and Training Seminar on Regional Development Planning for Disaster Prevention
5. , "Improved Fire Safety System in Developing Countries," United Nations Centre for Regional Development (UNCRD), October 17, 1994, Tokyo, Japan UNCRD Proceedings Series No. 7, p. 99-109 UNCRD, Nagoya, Japan.
6. Chow, W.K. · 1994
7. Chow, W.K. · 1995
8. Klote, J. · 1992
9. 10.1002/fam.81002020310.1002/fam.810020203 ↗
10. 10.1177/07349041930110040510.1177/073490419301100405 ↗
11. Peacock, R.D. · 1993