A case study of a pipe line burst in the Mihama Nuclear Power Plant
Source abstract
Abstract
Abstract On August ninth, 2004, at the Mihama nuclear power plant in Japan, a carbon steel pipe line carrying hot water under high pressure burst, killing five workers employed in maintenance job nearby. The major cause for the burst was presumed to be the pipe wall thinning due to so‐called erosion‐corrosion which had been revealed to be the cause of similar accident in 1986 at the Surry nuclear power plant in USA. However, the opinion of this author is that the wall thinning must have been caused through differential flow velocity corrosion accompanied with passivation, the origin of which was irregularities in the fluid flow velocity as well as in the pipe wall temperature. A rationale is presented that is consistent with this hypothesis. A countermeasure to this type of corrosion is also proposed.
Source: crossref · Quality: baseline
Research context
OpenAlex topics: Hydrogen embrittlement and corrosion behaviors in metals · Concrete Corrosion and Durability · Erosion and Abrasive Machining
SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.
References (6)
Show source-provided references
1. Kitashima N. · Boshoku Gijutsu (presently Zairyo‐to‐Kankyo) · 1986 · 35 · 633
2. Yanagida S. · J. High Press. Gas Safety Inst. Japan · 1999 · 36 · 720
3. 10.3323/jcorr1991.53.44010.3323/jcorr1991.53.440 ↗
4. Umemura F. · Boshoku Gijutsu (presently Zairyo‐to‐Kankyo) · 1981 · 30 · 276
5. O. de Bouvier M. Bouchacourt K. Fruzzetti presented at International Conference of Water Chemistry of Nuclear Reactor Systems Avignon France April 2002 pp. 22–26.
6. K. Fujita presented at The 10thCourse for Materials and Environments Chugoku‐Shikoku Branch of JSCE Okayama Japan 2004 pp. 31–35.