Convective heat dissipation with lattice-frame materials
Source abstract
Abstract
Abstract This paper presents experimental results on heat transfer and pressure drop for a compact heat sink made of fully triangulated, lightweight (porosity ∼ 0.938), aluminum lattice-frame materials (LFMs). Due to the inherent structural anisotropy of the LFMs, two mutually perpendicular orientations were selected for the measurements. Constant heat flux was applied to the heat sink under steady state conditions, and dissipated by forced air convection. The experimental data were compared with those predicted from an analytical model based on fin analogy. The experimental results revealed that pressure drop is strongly dependent upon the orientation of the structure, due mainly to the flow blockage effect. For heat transfer measurements, typical local temperature distributions on the substrate under constant heat flux conditions were captured with infrared camera. The thermal behavior of LFMs was found to follow closely that of cylinder banks, with early transition Reynolds number (based on strut diameter) equal to about 300. The Nusselt number prediction from the fin-analogy correlates well with experimental measurements, except at low Reynolds numbers where a slightly underestimation is observed. Comparisons with empty channels and commonly used heat exchanger media show that the present LFM heat sink can remove heat approximately seven times more efficient than an empty channel and as efficient as a bank of cylinders at the same porosity level. The aluminum LFMs are extremely stiff and strong, making them ideal candidates for multifunctional structures requiring both heat dissipation and mechanical load carrying capabilities.
Source: openaire · Quality: candidate unverified · Source record ↗
Research context
OpenAlex topics: Heat and Mass Transfer in Porous Media · Cellular and Composite Structures · Aerodynamics and Fluid Dynamics Research
SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.
References (17)
Show source-provided references
1. Bastawros, A.-F., Evans, A.G., Stone, H.A., 1998. Evaluation of cellular metal heat dissipation media. Technical Report MECH 325, DBAS, Harvard University
2. Bejan · 1995
3. Forced convection in high porosity metal foams10.1115/1.1287793 ↗
4. Effect of imperfections on the yielding of two-dimensional foams10.1016/S0022-5096(99)00030-7 ↗
5. A method of correlating forced convection heat transfer data and a comparison with fluid friction
6. Coleman · 1999
7. Effective properties of the octet-truss lattice material10.1016/S0022-5096(01)00010-2 ↗
8. Foam topology: bending versus stretching dominated architectures10.1016/S1359-6454(00)00379-7 ↗
9. Heat transfer in automobile radiators of the tubular type
10. Haack, D., Butcher, K., Kirn, T., Hodson, H.P., Lu, T.J., 2001. Novel lightweight metal foam heat exchanger. ASME International Mechanical Engineering Congress & Exposition, Proceedings V.3 (PID-4B: Heat Exchangers Applications for Change of Phase Media and Fuel Cells Systems, Book No. I00548), New York10.1115/IMECE2001/PID-25616 ↗
11. Kays · 1984
12. Forced convection in microstructures for electronic equipment cooling10.1115/1.2826027 ↗
13. Kim, T., Fuller, A.J., Hodson, H.P., Lu, T.J., 2002. An experimental study on thermal transport in lightweight metal foams at high Reynolds numbers. In: Proceedings of the International Symposium of Compact Heat Exchangers, Grenoble, France, pp. 227–232
14. Heat transfer efficiency of metal honeycombs10.1016/S0017-9310(98)00306-8 ↗
15. Ultralight porous metals: from fundamentals to applications10.1007/BF02486571 ↗
16. Heat transfer in open-cell metal foams10.1016/S1359-6454(98)00031-7 ↗
17. Zukauskas, A., 1987. Convective heat transfer in cross flow. In: Kakac, S., Shah, R.K., Aung, W. (Eds.), Handbook of Single-Phase Convective Heat Transfer, New York (Chapter 6)