Bench-scale tests on PMMA fires with water mist
Source abstract
Abstract
Abstract The effects of water mist on solid fires are more complicated than on liquid pool fires. Both the smoke and heat release rates would be very different. In this paper, the action of water mist on bench-scale solid fuel polymethylmethacrylate (PMMA) fires in a confined space under different external radiant heat fluxes has been studied. Small-scale PMMA fire tests with water mist application were developed in a cone calorimeter. Extinguishing mechanisms including oxygen displacement and cooling of the gas phase and fuel surface were studied. Water mist was generated by a single pressure nozzle in a cone calorimeter. Physical characteristics of the water mist were measured by Laser Doppler Velocimetry or the Adaptive Phase Doppler Velocimetry system (LDV/APV system). The heat release rate, oxygen, carbon dioxide, and carbon monoxide concentrations and other important parameters of the interaction under various conditions were measured. The results illustrated that water mist would suppress the diffusion flames induced by burning PMMA in a confined space by oxygen displacement, evaporation cooling and radiant heat attenuation. Combustion might be enhanced through expansion of the mixture and chain reaction. Suppression plays a dominating role when water mist of sufficient volumetric flow rate is applied. The flame can be suppressed more easily under poorer ventilation. Although only small-scale solid fuel PMMA fires were taken as examples to demonstrate the test, similar working principles also apply to other polymers.
Source: openaire · Quality: candidate unverified · Source record ↗
Research context
OpenAlex topics: Fire dynamics and safety research · Combustion and Detonation Processes · Flame retardant materials and properties
SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.
References (32)
Show source-provided references
1. The extinction of fires by water sprays
2. Incentive for use of misting sprays as a fire suppression flooding agent
3. The role of water in the suppression of fires
4. Codes of practice for minimum fire service installations and equipment and inspection, testing and maintenance of installations and equipment, Fire Services Department, Hong Kong. 1998.
5. National Fire Protection Association · 2002
6. National Fire Protection Association · 1996
7. Discussions on the use of fine water sprays or mists for fire suppression10.1016/0950-4230(95)90057-V ↗
8. A state-of-the-art review of water mist fire suppression research and development—1996
9. A closer look at the fire extinguishing properties of water mist10.3801/IAFSS.FSS.4-47 ↗
10. The role of fire dynamics in design of water mist fire suppression systems
11. Cabin water sprays for fire suppression: an experimental evaluation
12. Suppression within a simulated computer cabinet using an external water spray
13. Simulation of sprinkler-hot layer interaction using a field model10.1002/fam.810180604 ↗
14. Experimental study on the interaction of water mists with fires in the Confined Space
15. CFD modeling of liquid pool fire suppression using fine water sprays
16. Burning rate of a pool fire with downward-directed sprays10.1016/S0379-7112(96)00024-0 ↗
17. Calculated interaction of sprays with large scale buoyant flows10.1115/1.3246674 ↗
18. Interaction of a water mist with a buoyant methane diffusion flame10.1016/0379-7112(95)00029-1 ↗
19. Jet diffusion flame suppression using water sprays—an interim report10.1080/00102208408923801 ↗
20. A study of the extinguishment of vertical wood slabs in self-sustained burning by water spray application10.1080/00102207608946741 ↗
21. Effect of water spray on re-ignition characteristics of solid fuels10.3801/IAFSS.FSS.5-829 ↗
22. Radiant heat attenuation in fire water sprays
23. A model for attenuation of fire radiation through water droplets10.1016/0379-7112(89)90002-7 ↗
24. Characteristics of water mists for fire suppression in enclosures
25. Fan · 1993
26. Drysdale · 1998
27. Water mists measurement of the flow field of the water mist by 3D LDV
28. Advances in spray drop size and velocity measurement capabilities for the characterization of fire protection systems
29. Estimation of rate of heat releases by means of oxygen consumption measurements10.1002/fam.810040202 ↗
30. American Society for Testing and Materials · 2003
31. Rate of heat release measurement using the cone calorimeter10.1007/BF01911673 ↗
32. An experimental and theoretical study of mechanisms of fire suppression by water