Fault component integrated impedance-based pilot protection scheme for EHV/UHV transmission line with thyristor controlled series capacitor (TCSC) and controllable shunt reactor (CSR)
Source abstract
Abstract
This paper analyzes the fundamental frequency impedance characteristic of a thyristor controlled series capacitor (TCSC) and presents a novel transmission line pilot protection scheme based on fault component integrated impedance (FCII) calculated for a transmission line with TCSC and controllable shunt reactor (CSR). The FCII is defined as the ratio of the sum of the fault component voltage phasors of a transmission line with TCSC and CSR to the sum of the fault component current phasors where all the phasors are determined at both line’s terminals. It can be used to distinguish internal faults occurring on the line from external ones. If the fault is an external one the FCII reflects the line’s capacitive impedance and has large value. If the fault is an internal one on the line the FCII reflects the impedance of the equivalent system and the line and is relatively small. The new pilot protection scheme can be easily set and has the fault phase selection ability and also it is not affected by the capacitive current and the fault transition resistance. It is not sensitive to compensation level and dynamics of TCSC and CSR. The effectiveness of the new scheme is validated against data obtained in ATP simulations and Northwest China 750 kV Project.
Source: openaire · Quality: candidate unverified · Source record ↗
Research context
OpenAlex topics: Power Systems Fault Detection · HVDC Systems and Fault Protection · High-Voltage Power Transmission Systems
SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.
References (19)
Show source-provided references
1. An M. Some new results of electric power science. Sci China Tech Sci, 2011, 54: 1940–194210.1007/s11431-011-4459-0 ↗
2. Zhou X X, Guo J B, Lin J M, et al. The Thyristor Controlled Series Capacitors in Power System (in Chinese), Beijing: Science Press, 2009
3. Wang W Z, Peng X L, He S E. The operation and maintenance of Chen-Bi 220 kV TCSC (in Chinese). Power Syst Technol, 2007, 31(1): 50–55
4. Hingorani M G, Gyugyi L. Understanding FACTS. Piscataway: IEEE Press, 199910.1109/9780470546802 ↗
5. Mojtaba K, Tarlochan S S. Impact of TCSC on the protection of transmission lines. IEEE Trans Power Del, 2006, 21(1): 80–8710.1109/TPWRD.2005.858798 ↗
6. Dash P K, Samantaray S R, Pand G. Fault classification and section identification of an advanced series-compensated transmission line using support vector machine. IEEE Trans Power Del, 2007, 22(1): 67–7310.1109/TPWRD.2006.876695 ↗
7. Xu Z Y, Du Z Q, Ran L, et al. A current differential relay for a 1000 kV UHV transmission line. IEEE Trans Power Del, 2007, 22(3): 1392–139910.1109/TPWRD.2007.900274 ↗
8. Northwest Grid of China. The study of 750kV transmission line and reactor protection suitable to TCSC and CSR (in Chinese). Technical Report, Xi’an, 2007
9. Bi T, Yu Y, Huang S, et al. An accurate compensation method of distributed capacitance current in differential protection of UHV transmission line. Power Engineering Society General Meeting, IEEE, USA, 2005. 770–774
10. Zhang M, Dong X Z, Bo Z Q, et al. A new current differential protection scheme for two-terminal transmission lines. Power Engineering Society General Meeting, IEEE, USA, 2007. 1–610.1109/PES.2007.386235 ↗
11. Zheng Y P. Study on protection for transmission line with SC and recloser of double-circuit lines in same tower (in Chinese). Doctoral Dissertation, Wuhan: Wuhan University, 2004
12. Zhang Y N, Suonan J L. Phaselet-based current differential protection scheme based on transient capacitive current compensation. IET Gen Trans & Dist, 2008, 2(4): 469–47710.1049/iet-gtd:20070494 ↗
13. Suonan J L, Liu K, Song G B. A novel UHV/EHV transmission line pilot protection based on fault component integrated impedance. IEEE Trans Power Del, 2011, 26(1): 127–13410.1109/TPWRD.2010.2066292 ↗
14. Girgis A A, Sallam A A, El-din A K. An adaptive protection scheme for advanced series compensated (ASC) transmission line. IEEE Trans Power Del, 1998, 13(2): 414–42010.1109/61.660908 ↗
15. Song Y H, Johns A T, Xuan Q Y, Artificial neural network based protection scheme for controllable series-compensated EHV transmission lines. IEE Gen Trans & Dist, 1996, 143(6): 535–54010.1049/ip-gtd:19960681 ↗
16. Song Y H, Xuan Q Y, Johns A T. Protection scheme for EHV transmission systems with thyristor controlled series compensation using radial basis function neural networks. Elec Power Compon Syst, 1997, 25(5): 553–56510.1080/07313569708955759 ↗
17. Parikh U B, Das B, Maheshwari R P. Combined wavelet-SVM technique for fault zone detection in a series compensated transmission line. IEEE Trans Power Del, 2008, 23(4): 1789–179410.1109/TPWRD.2008.919395 ↗
18. Dong X Z, Ge Y Z, He J L. Surge impedance relay. IEEE Trans Power Del, 2005, 20(2): 1247–125610.1109/TPWRD.2004.838477 ↗
19. Dong X Z, Shi S X, Cui T, et al. Optimizing solution of fault location using single terminal quantities. Sci China Ser E-Tech Sci, 2008, 51(6): 761–77210.1007/s11431-008-0047-3 ↗