Exergy Analysis of an Air Conditioning Process
Source abstract
Abstract
The exergy analysis of an air conditioning process in wintertime is presented in this paper.This process consists of mixing outdoor air with conditioned air, heating, humidifying, and reheating the air mixture.The air is heated in the heat exchangers by warm water at a temperature of 80/60C and humidified by spraying water at a temperature of 12 C.The ratio of the mass flow rates of outdoor and conditioned air is varied, and it is upon this variable that the exergy analysis is performed.The five cases are analyzed with different outdoor air temperature values.It is shown that the heat transfer rate in the heat exchangers is the smallest at the ratio of mass flow rates of outdoor and conditioned air g 1 = 0.45.The greatest exergy destruction is apparent in the heat exchangers, and the maximum exergy efficiency of the whole process ex = 0.71 is achieved at the ratio g 1 = 0.45.According to the exergy criterion, this air conditioning is a relatively efficient process.
Source: openalex_inverted_index · Quality: baseline
Research context
OpenAlex topics: Advanced Control Systems Optimization · Process Optimization and Integration · Heat Transfer and Optimization
SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.
References
Reference metadata was not supplied for this record.