Experimental analysis of the effectiveness of emergency signage and its implementation in evacuation simulation
Source abstract
Abstract
SUMMARY Signage systems play an important role in aiding occupants during both circulation and evacuation. Despite the fact that signage systems are an important component in building wayfinding systems, there is a lack of relevant data regarding how occupants perceive, interpret and use the information conveyed by emergency signage. The effectiveness of signage systems is therefore difficult to assess. In this paper, we address this issue through experimentation. The experiment involved measuring the impact of a signage system on a population of 68 test subjects who were instructed to individually vacate a building as quickly as possible via any means they thought appropriate. The evacuation path involved a number of decision points at which emergency signage was available to identify the appropriate path. Through analysis of video footage and data derived from questionnaires, the number of people who saw and utilised the signage information to assist their egress is determined. The experimental results are used to enhance the existing signage model within the buildingEXODUS software. In particular, the signage detection and acceptance probabilities are assigned values based on the experimental data rather than the ideal values previously used in the model. The impact that the enhanced signage model has on evacuation analysis is demonstrated in a hypothetical evacuation scenario. The enhanced signage model is shown to produce a more conservative lower estimate of expected egress times. Copyright © 2011 John Wiley & Sons, Ltd.
Source: crossref · Quality: baseline
Research context
OpenAlex topics: Evacuation and Crowd Dynamics · Spatial Cognition and Navigation · 3D Modeling in Geospatial Applications
SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.
Affiliations
Fire Safety Engineering Group University of Greenwich UK
References (24)
Show source-provided references
1. Arthur P · 1992 · 76
2. 2002
3. 2000
4. Visibility through fire smoke
5. 10.3210/fst.5.7910.3210/fst.5.79 ↗
6. T Jin 1997 3 2110.3379/jmsjmag.21.S2_351 ↗
7. Jin T · 2002 · 2‐42
8. Paulsen T · 1994 · 693
9. T McClintock TJ Shields AH Reinhardt‐Rutland JC Leslie 2001 23 3310.1023/A:1010050823176 ↗
10. The Scandinavian Star Disaster of 7 April 1990.Main Report NOR 1991:1E.PDC:Aurskog Norway 1991 ISBN82‐583‐0236‐1.
11. Cook County Administration Building Fire Review prepared by James Lee Witt Associates LLC 2004.
12. W Grosshandler N Bryner D Madrzykowski K Kuntz 2005
13. Sixsmith A · 1988
14. Erica DK · 2008 · 3‐456
15. 10.1177/10423915960080020210.1177/104239159600800202 ↗
16. S Gwynne ER Galea M Owen PJ Lawrence L Filippidis 2000 1041 105210.3801/IAFSS.FSS.6-1041 ↗
17. Filippidis L · 2001 · 1529
18. 10.1177/104239150706402510.1177/1042391507064025 ↗
19. Filippidis L · 2003 · 39
20. 10.1177/104239150605429810.1177/1042391506054298 ↗
21. 10.3801/IAFSS.FSS.9‐38910.3801/IAFSS.FSS.9‐389 ↗
22. Gibson JJ · 1977 · 67
23. Gibson JJ · 1979
24. NFPA 1997