journal article·2016-04

Methane calibration burner and C‐factor determination with cone calorimeter – validation of the standardized calibration protocol

Eric Guillaume, Laurent Saragoza

Fire and Materials· Volume 40· Issue 3
Publisher page

Abstract

Summary The cone calorimeter is one of the major fire tests. In its reference standard ISO 5660‐1, the apparatus (and especially a characteristic of its orifice plate mass flow meter, called C‐Factor) is calibrated using a methane burner set at 5 kW. However, measurements performed in end‐use are in the range 1–10 kW. In addition, standard proposes to check linearity at 1 and 3 kW, which means in the lowest part of the range. This communication establishes the validation of the linearity on the whole range and determines the optimal condition for C‐factor determination. It justifies the technical choices of the standard. Copyright © 2014 John Wiley & Sons, Ltd.
Source: crossref · Quality: baseline

Research context

OpenAlex topics: Fire dynamics and safety research · Atmospheric chemistry and aerosols · Combustion and Detonation Processes

SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.

Affiliations

Laboratoire national de métrologie et d'essais (LNE) 1 rue Gaston Boissier 75724 Paris Cedex 15 France

References (14)

Show source-provided references
1. 10.6028/NBS.IR.82-261110.6028/NBS.IR.82-2611 ↗
2. 10.1002/fam.81008020610.1002/fam.810080206 ↗
3. Estimation of rate of heat release by means of oxygen consumption measurements10.1002/fam.810040202 ↗
4. 10.1007/BF0103844910.1007/BF01038449 ↗
5. 10.1080/1478644020863562710.1080/14786440208635627 ↗
6. ISO 5660‐1:2002.Reaction‐to‐fire tests – heat release smoke production and mass loss rate – part 1: heat release rate (cone calorimeter method).
7. 10.1023/A:101541600588810.1023/A:1015416005888 ↗
8. ZhaoL.Bench scale apparatus measurement uncertainty and uncertainty effects on measurement of fire characteristics of material system. Thesis Worcester Polytechnic Institute May2005.
9. 10.1007/s10694-008-0050-z10.1007/s10694-008-0050-z ↗
10. 10.1002/fam.94710.1002/fam.947 ↗
11. 10.1051/rfm/201200710.1051/rfm/2012007 ↗
12. 10.1002/fam.217410.1002/fam.2174 ↗
13. ISO 13927:2001.Plastics – simple heat release test using a conical radiant heater and a thermopile detector.
14. Mc Caffrey B · 1995 · 2.1