Abstract

Abstract A two‐storey test rig was used to investigate how an insulated facade would react to the impingement of a simulated room fire. In particular, whether or not a facade insulated with polyurethane foam would promote vertical flame spread. Wooden cribs weighing 40 kg were used as fire sources. One set of tests was run without any steel cladding to study the behaviour of the polyurethane foam alone. In a wall‐configuration test as well as under a conrner‐configuration one limited vertical and horizontal flame propagation were found. The degree of damage was to some extent, greater under the corner‐test conditions than with the wall tests. A ventilated facade construction with the profiled steel cladding fixed to vertical support‐work was used for the second set of tests. In order to simulate repair conditions, the outer metal cladding was completely removed from the lower 1.5 m of the facade. In Both tests a strong chimney‐effect behind the cladding was observed. This intensification of the flame impingement led to a flame spread up the top of the facade. The tests indicated that the vertical flame spread would continue unless the method of construction incorporated vertical fire stops.
Source: crossref · Quality: baseline

Research context

OpenAlex topics: Fire dynamics and safety research · Structural Analysis of Composite Materials · Flame retardant materials and properties

SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.

References (12)

Show source-provided references
1. Brandverhalten von Baustoffen und Bauteilen DIN 4102 Beuth‐Verlag GmbH Berlin (May1981).
2. H. G.Klingelhöfer Risikogerechte anwendungsbezogene Baustoff‐ Brandprüfung.DGFH HeftNr. 66/1982 Drittes Fachgespräch Brandverhalten und Feuerschutz von Holzkonstruktionen.
3. Fire Journal54(1982).
4. H.Zorgman Behaviour of insulated steel roofs in fully developed fires. 5th International Fire Protection Seminar Karlsruhe 1976.
5. Landesbauordnung Nordrhein‐Westfalen (NRW) (Building Regulation)23.
6. Brandschutztechnische Prüfung and Bewertung von Fassaden aus UP‐Hartschaum‐Leichtbeton
7. Klöker W. · Kunstoffe · 1977 · 67 · 8
8. Cahiers du Centre Scientifique et Technique du BâtimentNr. 71 1964. Règles Générales du Construction des Bâtiments d' Habitation.
9. Enfluss der Brandschutztechnischen Klassifizierung von Harten, OIR‐PUR‐Schaumstoffen auf das Brandverhalten von Wärmedämm‐verbundsystemen
10. F. H.Prager H.Rosteck W.Steuer R.Wiedermann andH.Karst Brandschutztechnische Prüfung und Bewertung der Hoesch‐isowand.VDFB58(1983).
11. F.Spiegelhalter Guide to design of cavity barriers and fire stops. BRE CP7/77.
12. J. J.Beitel andW. R.Evans SPI‐Test Series Final Reports Nos 1 and 2 (SWRI Project No. 01.6112) Multistorey Fire Evaluation Program.