journal article·2005-07

Test method for spalling of fire exposed concrete

K.D. Hertz, L.S. Sørensen

Fire Safety Journal· Volume 40· Issue 5
Publisher page

Abstract

A new material test method is presented for determining whether or not an actual concrete may suffer from explosive spalling at a specified moisture level. The method takes into account the effect of stresses from hindered thermal expansion at the fire-exposed surface. Cylinders are used, which in many countries serve as standard specimens for testing the compressive strength. Consequently, the method is quick, cheap and easy to use in comparison to the alternative of testing full-scale or semi full-scale structures with correct humidity, load and boundary conditions. A number of concretes have been studied using this method, and it is concluded that sufficient quantities of polypropylene fibres of suitable characteristics may prevent spalling of a concrete even when thermal expansion is restrained.
Source: openaire · Quality: candidate unverified · Source record ↗

Research context

OpenAlex topics: Fire effects on concrete materials · Structural Response to Dynamic Loads · Structural Behavior of Reinforced Concrete

SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.

References (12)

Show source-provided references
1. Limits of spalling of fire exposed concrete10.1016/S0379-7112(02)00051-6 ↗
2. Explosion of silica-fume concrete10.1016/0379-7112(84)90057-2 ↗
3. Hertz KD. Eksplosion og reststyrke af varmepåvirket silikabeton. (Explosion and residual strength of fire exposed silica fume concrete.) Report 162. Institute of Building Design (now Department of Civil Engineering), Technical University of Denmark; 1982. 12p. [in Danish].
4. Hertz KD. Heat induced explosion of dense concretes. Report 166. CIB W14/84/33(DK). Institute of Building Design (now Department of Civil Engineering), Technical University of Denmark; 1984. 20p.
5. Hertz KD. Danish investigations on silica fume concretes at elevated temperatures. Keynote speech at technical session fire resistance of materials and/or members made with high-strength concrete. ACI Spring Convention; 1991. ACI Mater J 1992;89(4):345–7.10.14359/9750 ↗
6. Gunnarsson JG. Eksplosiv afskalning af beton. (Explosive spalling of concrete.) M.Sc. thesis. Department of Buildings and Energy (now Department of Civil Engineering). 1998 [in Danish].
7. Kristiansen FH, Hertz KD, Sørensen LS. Eksplosiv afskalning af beton (Explosive spalling of concrete.) Report BYG.DTU R-050. Department of Civil Engineering; December 2003. 76p [in Danish]. http://www.byg.dtu.dk.
8. Hertz KD. Betonkonstruktioners brandtekniske egenskaber. Part 1 and 2 of Ph.D. thesis (Fire properties of concrete constructions), Report 140. Institute of Building Design (now Department of Civil Engineering), Technical University of Denmark; 1980. 210p.
9. Sørensen LS, Hertz KD, Kristiansen FH. Explosive spalling of fire exposed resource saving concrete structures. Nordic Mini-Seminar on Concrete and Fire, Danish Technological Institute; May 2003. 3p.
10. Jensen L. Spalling of concrete exposed to fire—the mitigating effect of polypropylene fibres. M.Sc. Project. Department of Civil Engineering, Technical University of Denmark; April 2003. 84p.
11. Persson B. Fire resistance of self-compacting concrete. SCC, Materials and Structures; 2002. 20pp, accepted for publication.
12. Persson B. Self-compacting concrete at fire temperatures. Report TVBM-3110. Lund Institute of Technology, Division of Building Materials, Lund; September 2003. 200p.