Experimental and numerical study of pool fire suppression using water mist
Source abstract
Abstract
Experiments in a real-scale room were done on water mist application to a pool fire. A fire produced with fuel oil in a 35 cm cylindrical pool was used, with a heat release rate reaching 75 kW in stationary conditions. Water application was studied with a nominal flow rate equal to 25 l/min provided by a set of four nozzles, injecting droplets with mean Sauter diameter equal to 112 μ m . Observations of fire suppression in these conditions showed two behaviors, which were analyzed and detailed with the help of numerical simulations conducted with FDS.v5. On one hand, a fast suppression (about 10 s required) was observed when water mist was applied to a developed fire. In this case, droplets were injected into a hot environment and thus evaporated strongly, generating a significant vapor concentration and resulting in a fast gas cooling and in an inerting effect. On the other hand, when the mist was applied early, fire growth was controlled, but its suppression required a longer application (about 1 min) and only occurred after a significant cooling of the flame and the liquid pool. These two mechanisms were detailed numerically through mass and energy balances for both the gas and the liquid phases and could help to derive suppression model improvements.
Source: openaire · Quality: candidate unverified · Source record ↗
Research context
OpenAlex topics: Fire dynamics and safety research · Combustion and Detonation Processes · Evacuation and Crowd Dynamics
SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.
References (21)
Show source-provided references
1. Fire suppression by water sprays
2. Review of water mist fire suppression systems—fundamental studies
3. J.R. Mawhinney, G.G. Back III, Water mist fire suppression systems, SFPE Handbook of Fire Protection Engineering, 2002, pp. 4.311–4.337.
4. On the flame structure at the base of a pool fire interacting with a water mist10.1016/S0894-1777(02)00247-9 ↗
5. Extinction limit of a pool fire with a water mist10.1016/S0379-7112(97)00011-8 ↗
6. Burning rate of a pool dire with downward-directed sprays10.1016/S0379-7112(96)00024-0 ↗
7. Interaction of water mists with a diffusion flame in a confined space10.1016/S0379-7112(99)00020-X ↗
8. Extinction of gas and liquid pool fires with water sprays10.1016/S0379-7112(02)00085-1 ↗
9. An experimental and numerical study on fire suppression using a water mist in an enclosure10.1016/S0360-1323(03)00134-3 ↗
10. Experimental investigation and numerical simulation of a furnished office fire10.1016/j.buildenv.2010.06.003 ↗
11. Experimental and numerical study on water mist suppression system on room fire10.1016/j.buildenv.2010.04.017 ↗
12. Calculation of fire extinguishment time with water mist in an enclosed room10.1007/s11630-010-0424-7 ↗
13. Comparison of FDS predictions by different combustion models with measured data for enclosure fires10.1016/j.firesaf.2010.06.002 ↗
14. CFD investigation of large scale pallet stack fires in tunnels protected by water mist systems10.1177/1042391510367359 ↗
15. Experimental and numerical study of fire in a midscale test tunnel10.1016/j.firesaf.2011.09.009 ↗
16. J. Vaari, J. Floyd, R. McDermott, CFD simulations on extinction of co-flow diffusion flames, in: 10th International Symposium on Fire Safety Science University of Maryland, USA, June 2011.10.3801/IAFSS.FSS.10-781 ↗
17. K.B. McGrattan, S. Hostikka, J.E. Floyd, Fire Dynamics Simulator (version 5), User׳s Guide. Technical Report, National Institute of Standards and Technology, 2007.10.6028/NIST.SP.1019-5 ↗
18. K.B. McGrattan, S. Hostikka, J.E. Floyd, Fire Dynamics Simulator (version 5), Technical Reference Guide, Technical Report, National Institute of Standards and Technology, 2007.10.6028/NIST.SP.1018-5 ↗
19. A. Jenft, Etude des interactions entre phénomènes d׳incendie et systèmes d׳extinction à eau. Développement d׳un module d׳extinction dans le logiciel FDS (PhD thesis), Université de Lorraine, 2013.
20. H.Z. Yu, J. Lee, H.C. Kung, Suppression of rack-storage fires by water, in: 4th International Symposium on Fire Safety Science Ottawa Congress Centre, Canada, Juillet, 1994.10.3801/IAFSS.FSS.4-901 ↗
21. Energy balance in a large compartment fire10.1016/j.firesaf.2007.08.002 ↗