Experimental study on fire spread behavior of single 110 kV cable under different layout conditions
Source abstract
Abstract
High-voltage cable fire accidents can cause large-scale power outages. In particular, the 110 kV large-section (diameter 10 cm) cable has complex cable structures. Therefore, based on the actual cable laying scenarios, three cable layout conditions are set, including the horizontal cable above horizontal floor structure (HCAHFS), the inclined cable above horizontal floor structure (ICAHFS), and the inclined cable above inclined floor structure (ICAIFS). The combustion behaviors and flame spread characteristics of 110 kV large-section cable are experimentally studied. It is found that the flame cannot spread on the surface of the flame-retardant outer sheath of the cable. However, when the cable-floor distance (lcf) is between 0.75 d and 2 d (d is the cable diameter) in HCAHFS, i.e. there is a floor under the cable that can catch cable melt, and the flame spread characteristics is different. After the cable is ignited, the cable fire can be divided into two parts, outer sheath flame and melt flame, and the cable fire can spread under the joint action of two flames. When lcf ≤ 0.75 d, the space under the cable is narrow. With the accumulation of melt on the floor, air entrainment is limited during cable combustion, resulting in the cable flame unsustainable. When lcf ≥ 2 d, the thermal radiation and convection from the melt and outer sheath flame to the cable preheat zone are weakened, resulting in cable flame extinction as well. In ICAHFS, the cable flame spread rate is first increased and then decreased with the increasing lcf at the fixed inclination angle; In ICAIFS, the upward spread rate of cable flame is faster than the downward spread rate at the fixed inclined angle. Moreover, the cable flame spread rate (FSR) in HCAHFS is the slowest compared to that in ICAIFS with different inclined angles. The preheating length for ICAIFS increases under both upper and lower ignition modes, while it is obviously at upper ignition, due to the melt flow. Finally, a correlation of FSR was proposed for various ignition positions and inclined angles. This study provides a reference for fire protection design and numerical simulation parameter setting of 110 kV cable fire.
Source: expertdata · Quality: candidate unverified · Source record ↗
Research context
OpenAlex topics: Fire dynamics and safety research · Lightning and Electromagnetic Phenomena · Fire Detection and Safety Systems
SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.
References (37)
Show source-provided references
1. A review of fundamental combustion phenomena in wire fires10.1007/s10694-019-00918-5 ↗
2. A numerical and experimental study of the ignition of insulated electric wire with long-term excess current supply under microgravity10.1016/j.proci.2016.06.134 ↗
3. Can a spreading flame over electric wire insulation in concurrent flow achieve steady propagation in microgravity?10.1016/j.proci.2018.05.007 ↗
4. Upward flame spread and critical conditions for PE/PVC cables in a tray configuration10.3801/IAFSS.FSS.4-433 ↗
5. A comparative study of bench-scale flammability properties of electric cables with different covering materials10.1177/073490419801600304 ↗
6. Burning of polymeric coatings on copper wires and glass threads: I. Flame propagation velocity10.1016/0010-2180(81)90036-5 ↗
7. Experimental study on combustion and flame spread characteristics in horizontal arrays of discrete fuels10.1016/j.combustflame.2020.10.049 ↗
8. Ignition limits of short-term overloaded electric wires in microgravity10.1016/j.proci.2012.06.064 ↗
9. Scale modeling of flame spread over PE-coated electric wires
10. Limiting oxygen concentration (LOC) of burning polyethylene insulated wires under external radiation10.1016/j.firesaf.2016.09.004 ↗
11. Flame spread over horizontal and vertical wires: the role of dripping and core10.1016/j.firesaf.2017.03.047 ↗
12. A numerical and experimental study of the ignition of insulated electric wire with long-term excess current supply under microgravity10.1016/j.proci.2016.06.134 ↗
13. Fire behaviors of flame-retardant cables part i: decomposition, swelling and spontaneous ignition10.1016/j.firesaf.2017.10.005 ↗
14. Mcgrattan · 2008 · vol. 3 · 1
15. Cable heat release, ignition, and spread in tray installations during fire (CHRISTIFIRE)
16. Improved assessment of fire spread over horizontal cable trays supported by video fire analysis10.1007/s10694-018-0788-x ↗
17. Cable tray fire tests with halogenated electric cables in a confined and mechanically ventilated facility10.1002/fam.2717 ↗
18. Cable tray FIRE tests simulations in open atmosphere and in confined and mechanically ventilated compartments with the CALIF3S/ISIS CFD software10.1002/fam.2680 ↗
19. Fire behavior of halogen-free flame retardant electrical cables with the cone calorimeter10.1016/j.jhazmat.2017.08.027 ↗
20. Flame spread over electric wire with high thermal conductivity metal core at different inclinations10.1016/j.proci.2014.05.059 ↗
21. Concurrent flame spread and blow-off over horizontal thin electrical wires10.1007/s10694-018-0785-0 ↗
22. The interaction between fuel inclination and horizontal wind: experimental study using thin wire10.1016/j.proci.2018.05.131 ↗
23. Analysis of upward- and downward flame spread over vertical installed polyethylene-insulated electrical wires10.1016/j.combustflame.2021.111896 ↗
24. Effect of transverse flow on flame spread and extinction over polyethylene-insulated wires10.1016/j.proci.2020.06.228 ↗
25. Burning behavior of cable tray located on a wall with different cable arrangements10.1002/fam.2669 ↗
26. Experimental investigation on maximum ceiling jet temperature generated by a vertically spreading cable fire10.1016/j.firesaf.2020.103125 ↗
27. Improved model for estimating sidewall effect on the fire heat release rate of horizontal cable tray10.1016/j.psep.2021.03.040 ↗
28. Effects of interlayer distance and cable spacing on flame characteristics and fire hazard of multilayer cables in utility tunnel10.1016/j.csite.2020.100784 ↗
29. Experimental study on flammability and flame spread characteristics of polyvinyl chloride (PVC) cable10.3390/polym12122789 ↗
30. Flame spread over horizontal and vertical wires: the role of dripping and core10.1016/j.firesaf.2017.03.047 ↗
31. The influence of currents on the ignition and correlative smoke productions for PVC-insulated electrical wires10.1007/s10694-016-0634-y ↗
32. Dripping behavior effects on flame propagation along electrical wires under high currents10.1016/j.firesaf.2021.103368 ↗
33. Downward flame spreading over electric wire under various oxygen concentrations10.1016/j.proci.2018.05.074 ↗
34. Flame spread over inclined electrical wires with AC electric fields10.1016/j.combustflame.2017.07.010 ↗
35. Flame spread over electrical wire with AC electric fields: internal circulation, fuel vapor-jet, spread rate acceleration, and molten insulator dripping10.1016/j.combustflame.2014.10.009 ↗
36. Effect of AC electric field on flame spread in electrical wire: variation in polyethylene insulation thickness and di-electrophoresis phenomenon10.1016/j.combustflame.2019.01.007 ↗
37. Quintiere · 2006