journal article·2006-01

Heating at Electrical Contacts: Characterizing the Effects of Torque, Contact Area, and Movement on the Temperature of Residential Receptacles

J. L. Ferrino-McAllister, R. J. Roby, J. A. Milke

Fire Technology· Volume 42· Issue 1
Publisher page

Abstract

Testing was performed using 120 volt, 15-amp receptacles and copper wire to determine the effect of torque and wire contact area on temperature elevation at receptacle screw terminals. Torque was varied on both the hot and neutral terminals from 0 to 12 in-lbs, and the apparent wire contact at the screw terminal was varied by 1/8″ and 5/8″. There was no significant difference in temperature when changing apparent wire contact. Increased temperatures were observed with reduced torque, however, they were not significant enough to initiate a glowing connection, nor high enough to cause rapid oxidation. Further testing showed that movement of a loose connection was necessary to cause significantly high temperature changes, arcing and sparking, rapid oxidation, and in some cases, glowing connections.
Source: openaire · Quality: candidate unverified · Source record ↗

Research context

OpenAlex topics: Building Energy and Comfort Optimization · Elevator Systems and Control

SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.

References (17)

Show source-provided references
1. Meese and Beausoliel, Exploratory Study of Glowing Electrical Connections, National Bureau of Standards, Washington, DC, Oct. 1976.10.6028/NBS.IR.76-1011 ↗
2. J. Aronstein, Fire Due to Overheating Aluminum Wired Branch Circuit Connections, Ballston Spa, NY: Wright Malta Corporation, Jan. 1981.
3. J. Aronstein, Study of Overheating of Aluminum-Wired Electrical Receptacles in Scarborough, Toronto, Homes, Ballston Spa, NY: Wright Malta Corporation, Jan. 1982.
4. B. Beland, Electricity as a Cause of Fires, Society of Fire Protection Engineers, Boston, MA, May 1984.
5. B. Ettling, “Glowing Connections,” The Fire and Arson Investigator, vol. 33, no. 3, March 1983, pp. 3–5.
6. Spletzer and Horine, Description and Testing of an Apparatus for Electrically Initiating Fires Through Simulation of a Faulty Connection, Sandia National Laboratories, Albuquerque, New Mexico, June 1986.
7. Hagimoto, Kinoshita, and Hagiwara, Glowing Phenomenon at the Contact of Different Kind of Metals, Annual Meeting of Japan Society for Safety Engineering
8. Hagimoto, Kinoshita, and Hagiwara, “Phenomenon of Glow at the Electrical Contacts of Copper Wires,” National Research Institute of Police Science Reports—Research on Forensic Science, vol. 41, no. 3, Aug. 1988.
9. J. Sletback, R. Kristensen, H. Sundklakk, G. Navik, and M. Runde, “Glowing Contact Areas in Loose Copper Wire Connections,” in 1991 Proceedings of the 37th IEEE Holm Conference on Electrical Contacts, IEEE, 1991, pp. 244–248.10.1109/HOLM.1991.170830 ↗
10. R. Brugger, “Glowing Electrical Connections,” Journal of the National Academy of Forensic Engineers, vol. IX, no. 1, June 1992, pp. 21–33.
11. R. Holm, Electrical Contacts: Theory and Applications, 4th edition, New York, NY: Springer-Verlag, 1967.10.1007/978-3-662-06688-1 ↗
12. NFPA 70: National Electrical Code, 1999 edition, National Fire Protection Association, Quincy, MA
13. D. R. Askeland, The Science and Engineering of Materials, 2nd edition, Boston, MA: PWS-Kent Publishing Company, 1989.
14. W. Callister, Materials Science and Engineering: An Introduction, 4th edition, New York, NY: John Wiley & Sons, Inc., 1997.
15. A. Ronnquist and H. Fischmeister, “The Oxidation of Copper, Rev. of Data, J. Institute of Metals, Oct. 1960, pp. 65–112.
16. A. Ronnquist, “The Oxidation of Copper,” Journal of the Institute of Metals, vol. 91, no. 89, 1962, pp. 105, 112
17. Leviton Technical Support, Verbal Communication, Aug. 2002.