A Relative Time Analysis of the Performance of Residential Smoke Detection Technologies
Source abstract
Abstract
A statistical study was conducted to compare the performance of different residential smoke detector technologies when exposed to different fire types. In order to facilitate comparisons between different fire and smoke growth rates, a non-dimensional smoke detector activation relative time was employed. Data from four major experimental studies was analyzed utilizing the relative time approach. The Common Language Effect Size, a measure of the probability that a particular detector technology will be the first to detect a fire of a particular type, was used to assess detector performance. The analysis confirmed previous results that ionization detectors, on average, respond faster to flaming fires, and that photoelectric detectors, on average, respond faster to smoldering fires. More importantly, this study also determined that the responses of ionization, photoelectric, and combination technologies are statistically equivalent for any given future residential fire That is, it cannot be determined with confidence which detector technology will alarm first to the next fire. Additionally, the analysis found that this statistical equivalence between detector technologies has not changed in the last 35 years despite increased fire growth rates associated with changes in furniture materials over that same time span.
Source: openaire · Quality: candidate unverified · Source record ↗
Research context
OpenAlex topics: Fire Detection and Safety Systems · Evacuation and Crowd Dynamics · Fire dynamics and safety research
SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.
References (7)
Show source-provided references
1. Bukowski RW, Waterman TE, Christian WJ (1975) Detector sensitivity and siting requirements for dwellings. NIST GCR 75–51, National Institute of Standards and Technology
2. Harpe SW, Waterman TE, Christian WJ (1977) Detector sensitivity and siting requirements—phase 2, NBS GCR 77–82, National Institute of Standards and Technology
3. Su JZ, Crampton GP, Carpenter DW, McCartney C, Leroux P (2003) Kemano fire studies—part 1: response of residential smoke alarms, research report 108, National Research Council of Canada
4. Bukowski RW, Peacock RD, Averill JD, Cleary TG, Bryner NP, Walton WD, Reneke PA, Kuligowski ED (2003) Performance of home smoke alarms: analysis of the response of several available technologies in residential fire settings, NIST TN 1455
5. McGraw KO, Wong SP (1992) A common language effect size statistic. Psychological bulletin 111(2)10.1037//0033-2909.111.2.361 ↗
6. UL Standard for Safety for Single and Multiple Station Smoke Alarms (2006) UL 217, 6th edn, dated August 25, 2006. Underwriters Laboratories Inc
7. UL Standard for Safety for Smoke Detectors for Fire Alarm Signaling Systems (2006) UL 268, 5th edn, dated September 8, 2006. Underwriters Laboratories