journal article·2016-03

Doorway Flows Induced by the Combined Effects of Natural and Forced Ventilation in Case of Multi-compartments Large-Scale Fire Experiments

Hugues Pretrel, Amine Koched, Laurent Audouin

Fire Technology· Volume 52· Issue 2
Publisher page

Abstract

This paper deals with the combined effects of fire and mechanical ventilation on the bi-directional flow occurring at a doorway for a fire scenario involving a three-compartment assembly. Based on large-scale fire tests, the analysis focused on three issues: the velocity profiles at the doorway, the location of the neutral plane, and the inflow and outflow rates entering and leaving the fire compartment. The combined effect of fire and mechanical ventilation leads to different flow regimes depending on whether the smoke outflow (or the fresh air inflow) and the forced ventilation are directed in the same direction or in opposite directions. The theoretical description based on the Bernoulli approach for natural convection flow is applied in case of the combined effect of buoyancy and inertia. Five configurations are identified: one-directional flow of smoke, bi-directional flow with upper smoke flow as dominant, natural convection case with equal smoke and fresh air flows, bi-directional flow with lower fresh air flow as dominant, and one-directional flow with only fresh air flow. These regimes are observed experimentally and clearly defined theoretically. A satisfactory agreement is obtained between the theory and the experiments. This approach permits identifying the critical conditions under which one-directional flow is encountered at the doorway.
Source: openaire · Quality: candidate unverified · Source record ↗

Research context

OpenAlex topics: Fire dynamics and safety research · Wind and Air Flow Studies · Evacuation and Crowd Dynamics

SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.

References (28)

Show source-provided references
1. Mowrer FW (2009) Driving forces for smoke movement and management. Fire Technol 45:147–162. 10.1007/s10694-008-0077-110.1007/s10694-008-0077-1 ↗
2. Lidwell OM (1997) Air exchange through doorways, the effect of temperature difference, turbulence and ventilation flow, J Hyg 79:141–154. 10.1017/S002217240005293110.1017/S0022172400052931 ↗
3. Dalziel SB, Lane-Serff GF (1991) The hydraulics of doorway exchange. J Build Environ 26:121–135. 10.1016/0360-1323(91)90019-810.1016/0360-1323(91)90019-8 ↗
4. Quintiere JG, DenBraven K (1978) Some theoretical aspects of fire induced flows through doorways in a room-corridor scale model, NBSIR 78-1512, Gaithersburg10.6028/NBS.IR.78-1512 ↗
5. Prahl J, Emmons HW (1975) Fire induced flow through an opening, Combust Flame 25:369–385. 10.1016/0010-2180(75)90109-110.1016/0010-2180(75)90109-1 ↗
6. Zukosky EE, Kubota T, Lim CS (1985) Experimental study of environment and heat transfer in a room fire. Mixing in doorway flows and entrainment in fires plumes, Report NBS-GCR-85-493, NIST, Gaithersburg
7. Nakaya J, Tanaka T, Yoshida M, Steckler K (1986) Doorway flow induced by a propane fire. Fire Saf J 10:185–195. 10.1016/0379-7112(86)90015-910.1016/0379-7112(86)90015-9 ↗
8. Karlsson B, Quintiere JG (2000) Enclosure fire dynamics. CRC Press, Boca Raton
9. Phillips JC, Woods AW (2004) On ventilation on heated room through a single doorway. J Build Environ 39:241–253. 10.1016/j.buildenv.2003.09.00210.1016/j.buildenv.2003.09.002 ↗
10. Stavrakakis GM, Markatos NC (2009) Simulation of airflow in one and two enclosures containing fire source. Int J Heat Mass Transfer 52:2690–2703. 10.1016/j.ijheatmasstransfer.2007.10.04610.1016/j.ijheatmasstransfer.2007.10.046 ↗
11. Chow WK, Zou GW (2005) Correlation equations on fire-induced air flow rates through doorway derived by large Eddy simulation. Build Environ 40:897–906. 10.1016/j.buildenv.2004.09.01010.1016/j.buildenv.2004.09.010 ↗
12. Suard S, Koched A, Pretrel H, Audouin L (2015) Numerical simulations of fire-induced doorway flows in a small scale enclosure. Int J Heat Mass Transfer 81:578–59010.1016/j.ijheatmasstransfer.2014.10.069 ↗
13. Bryant RA (2009) A comparison of gas velocity measurements in a full-scale enclosure fire. Fire Saf J 44:793–800. 10.1016/j.firesaf.2009.03.01010.1016/j.firesaf.2009.03.010 ↗
14. Wang L, Quintiere JG (2009) An analysis of compartment fire doorway flow. Fire Saf J 44:718–731. 10.1016/j.firesaf.2009.02.00110.1016/j.firesaf.2009.02.001 ↗
15. Wang L, Quintiere JG (2009) A general formula for the prediction of vent flows. Fire Saf J 44:789–792, 10.1016/j.firesaf.2009.03.01210.1016/j.firesaf.2009.03.012 ↗
16. Xiao B (2012) Comparison of numerical and experimental results of fire induced doorway flows. Fire Technol 48:595–614. doi: 10.1007/s10694-009-0131-710.1007/s10694-009-0131-7 ↗
17. Crocker JP, Rangwala AS, Dembsey NA, LeBlanc DJ (2009) Investigation of sprinkler sprays on fire induced doorway flows. Fire Technol 46:347–362. doi: 10.1007/s10694-009-0081-010.1007/s10694-009-0081-0 ↗
18. Pretrel H, Audouin L (2010) Smoke movement induced by buoyancy and total pressure between two confined and mechanically ventilated compartments. In: Proceedings of the 2010 Interflam conference, Interscience Communications Limited, pp 1053–1065
19. Beyler C (1991) Analysis of compartment fires with overhead forced ventilation. In: Proceedings of the third international symposium, International Association for Fire Safety Science, pp 291–300.10.3801/IAFSS.FSS.3-291 ↗
20. Le Saux W, Pretrel H, Lucchesi C, Guillou P (2009) Experimental study of the fire mass loss rate in confined and mechanically ventilated multi-room scenarios. Fire Saf Sci 9:943–954. 10.3801/IAFSS.FSS.9-94310.3801/IAFSS.FSS.9-943 ↗
21. Pretrel H, Such JM (2005) Effect of ventilation procedures on the behaviour of a fire compartment scenario. Nucl Eng Des 235:2155–2169. 10.1016/j.nucengdes.2005.03.00310.1016/j.nucengdes.2005.03.003 ↗
22. Pretrel H, Le Saux W, Audouin L (2012) Pressure variations induced by a pool fire in a well-confined and force-ventilated compartment, Fire Saf J 52:11–24. 10.1016/j.firesaf.2012.04.00510.1016/j.firesaf.2012.04.005 ↗
23. Pretrel H, Audouin L (2011) Doorway flows induced by the combined effects of natural and forced ventilation in a three compartment assembly. In: Proceedings of the tenth International Symposium on Fire Safety Science, Maryland, USA, 19–24 June 201110.3801/IAFSS.FSS.10-1015 ↗
24. Koched A, Pretrel H, Vauquelin O, Audouin L (2014) Experimental determination of the discharge coefficient at a doorway for fire induced flow in natural and mixed convection. Fire Mater. doi: 10.1002/fam.2272
25. Pretrel H, Le Saux W, Audouin L (2014) Heat release rate calculation for fire in closed and mechanically ventilated compartments with OC and CDG calorimetry. Fire Mater 38:474–50610.1002/fam.2193 ↗
26. Audouin L, Tourniaire B (1999) New estimation of the thermal interface height in forced-ventilation enclosure fires, In: International Symposium of Fire Safety Science10.3801/IAFSS.FSS.6-555 ↗
27. Pretrel H, Audouin L (2015) New developments in data regression methods for the characterization of thermal stratification due to fire. Fire Saf J 76:54–6410.1016/j.firesaf.2015.05.004 ↗
28. Pretrel H, Le Saux W (2005) Experimental study of the burning rate behaviour of a pool fire in confined and ventilated compartment, Post-SMIRT 18, Vienna10.3801/IAFSS.FSS.8-1217 ↗