Ignition and Charring of PVC-Based Electric Cables
Source abstract
Abstract
The ignition of four different PVC-based electric cables was studied using cone calorimeter and the influence of the charring phenomenon on ignition was investigated. The thermophysical and optical properties of the sheaths before decomposition were measured. The kinetics of charring was studied by photogrammetry. It was shown that charring occurs for three cables before ignition at heat flux lower than 45 kW/m2. The lower is the heat flux, the higher is the char amount at ignition. In spite of the char formation, it was observed that the time-to-ignition of the cables can be properly calculated using the well-known Quintiere’s equation, considering an apparent temperature of ignition. This apparent temperature at ignition was found in the range 312°C to 349°C for the four electric cables.
Source: openaire · Quality: candidate unverified · Source record ↗
Research context
OpenAlex topics: Flame retardant materials and properties · Fire dynamics and safety research · Combustion and Detonation Processes
SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.
References (25)
Show source-provided references
1. Zavaleta P, Hanouzet R, Beji T (2019) Improved assessment of fire spread over horizontal cable trays supported by video fire analysis. Fire Technol 55:233–25510.1007/s10694-018-0788-x ↗
2. Huang X, Nakamura Y (2020) A review of fundamental combustion phenomena in wire fires. Fire Technol 56:315–36010.1007/s10694-019-00918-5 ↗
3. Huang X, Zhu H, Peng L, Zheng Z, Zeng W, Bi K, Cheng C, Chow W (2019) Thermal characteristics of vertically spreading cable fires in confined compartments. Fire Technol 55:1849–187510.1007/s10694-019-00833-9 ↗
4. McGrattan K, Lock A, Marsh N, Nyden M, Price M, Morgan AB, Galaska M, Schenck K (2010) Cable heat release, ignition, and spread in tray installations during fire (Christifire) Volume 1: Horizontal Trays, United States Nuclear Regulatory Commission, Washington DC
5. Coaker A, Hirschler M, Shoemaker C (1992) Rate of heat release testing for vinyl wire and cable materials with reduced flammability and smoke full-scale cable tray tests and small-scale tests. Fire Saf J 19:19–5310.1016/0379-7112(92)90004-V ↗
6. Rhodes BT, Quintiere JG (1996) Burning rate and flame heat flux for PMMA in a cone calorimeter. Fire Saf J 26:221–24010.1016/S0379-7112(96)00025-2 ↗
7. Quintiere JG (2001) The effects of angular orientation on flame spread over thin materials. Fire Saf J 36:291–31210.1016/S0379-7112(00)00051-5 ↗
8. Lyon R, Quintiere J (2007) Criteria for piloted ignition of combustible solids. Combust Flame 151:551–55910.1016/j.combustflame.2007.07.020 ↗
9. Schartel B, Hull R (2007) Development fire-retarded materials—interpretation of cone calorimeter data. Fire Mater 31:327–35410.1002/fam.949 ↗
10. Hopkins D Jr, Quintiere JG (1996) Material fire properties and predictions for thermoplastics. Fire Saf J 26:241–26810.1016/S0379-7112(96)00033-1 ↗
11. Bal N, Rein G (2011) Numerical investigation of the ignition delay time of a translucent solid at high radiant heat fluxes. Combust Flame 158:1109–111610.1016/j.combustflame.2010.10.014 ↗
12. Boulet P, Parent G, Acem Z, Collin A, Försth M, Bal N, Rein G, Torero J (2014) Radiation emission from a heating coil or a halogen lamp on a semitransparent sample. Int J Therm Sci 77:223–23210.1016/j.ijthermalsci.2013.11.006 ↗
13. Girods P, Bal H, Biteau H, Rein G, Torero J (2011) Comparison of pyrolysis behavior results between the cone calorimeter and the fire propagation apparatus heat sources. Fire Saf Sci 10:889–90110.3801/IAFSS.FSS.10-889 ↗
14. Sonnier R, Bokobza L, Concha-Lozano N (2015) Influence of multiwall carbon nanotube (MWCNT) dispersion on ignition of poly(dimethylsiloxane)–MWCNT composites. Polym Adv Technol 26:277–28610.1002/pat.3454 ↗
15. Sonnier R, Ferry L, Gallard B, Boudenne A, Lavaud F (2015) Controlled emissivity coatings to delay ignition of polyethylene. Materials 8:6935–694910.3390/ma8105349 ↗
16. Oztekin E, Crowley S, Lyon R, Stoliarov S, Patel P, Hull R (2012) Sources of variability in fire test data: a case study on poly(aryl ether ether ketone) (PEEK). Combust Flame 159:1720–173110.1016/j.combustflame.2011.11.009 ↗
17. Meinier R, Sonnier R, Zavaleta P, Suard S, Ferry L (2018) Fire behavior of halogen-free flame retardant electrical cables with the cone calorimeter. J Hazard Mater 342:306–31610.1016/j.jhazmat.2017.08.027 ↗
18. Gong T, Xie Q, Huang X (2018) Fire behaviors of flame-retardant cables part I: decomposition, swelling and spontaneous ignition. Fire Saf J 95:113–12110.1016/j.firesaf.2017.10.005 ↗
19. Zavaleta P, Suard S, Audouin L (2019) Cable tray fire tests with halogenated electric cables in a confined and mechanically ventilated facility. Fire Mater 43:543–56010.1002/fam.2717 ↗
20. Siemon M, Riese O, Forell B, Krönung D, Klein-Heßling W (2019) Experimental and numerical analysis of the influence of cable tray arrangements on the resulting mass loss rate and fire spreading. Fire Mater 43:497–513. https://doi.org/10.1002/fam.268910.1002/fam.2689 ↗
21. Decimus A, Sonnier R, Zavaleta P, Suard S, Ferry L (2019) Study of gases released under incomplete combustion using PCFC–FTIR. J Therm Anal Calorim 138:753–76310.1007/s10973-019-08160-5 ↗
22. Boulet P, Parent G, Acem Z, Rogaume T, Fateh T, Zaida J, Richard F (2012) Characterization of the radiative exchanges when using a cone calorimeter for the study of the plywood pyrolysis. Fire Saf J 51:53–6010.1016/j.firesaf.2012.03.003 ↗
23. Beyler C , Hirschler M (2002) Thermal decomposition of polymers, SFPE handbook of Fire Protection Engineering, 3rd edn, Section 1, Chapter 7. ISBN: 087765-451-4
24. Courty L, Garo JP (2017) External heating of electrical cables and auto-ignition investigation. J Hazard Mater 321:528–53610.1016/j.jhazmat.2016.09.042 ↗
25. Tewarson A (2002) Generation of heat and chemical compound in fires, SFPE handbook of fire protection engineering, ISBN:087765-451-4, Third edition, Section three, Chapter 4