journal article·2024-05Open access

The Development of Automatic Sprinkler System Concepts for Maritime Vehicle Carriers

Magnus Arvidson, Örjan Westlund

Fire Technology· Volume 60· Issue 3

Abstract

Abstract Closed ro-ro spaces on maritime vehicle carriers are usually protected by a total-flooding carbon dioxide system. Such systems have many benefits, for example that there are no residues that can adversely affect the protected objects (in this case thousands of vehicles) and the agent is electrically non-conductive. However, there could be a considerable time delay from the start of a fire until the carbon dioxide system is discharged. Experience has shown that this delay time can cause significant fire damage and jeopardize the performance of the system. Within the EU funded LASH FIRE project, design and installation guidelines for supplementary automatic water-based fire sprinkler systems were developed. An important design feature is that the system automatically activates at an early stage of a fire. This would allow more time to fight the fire manually or to safely evacuate the space and discharge the CO2 system when the fire is controlled to one or a few vehicles instead of at a time when it has escalated in size. The work was partly based on a comprehensive literature review that identified relevant standards and information applicable to the design of automatic fire sprinkler and deluge water spray systems. Large-scale fire tests verified that the suggested system designs were able to provide control of realistic vehicle fires, including fires in passenger cars and a freight truck.
Source: crossref · Quality: baseline

Research context

OpenAlex topics: Fire dynamics and safety research · Evacuation and Crowd Dynamics · Fire Detection and Safety Systems

SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.

References (20)

Show source-provided references
1. Fire aboard vehicle carrier courage. Accident no: DCA15RM024, National Transportation Safety Board Marine Accident Brief. Issued 29 Jun 2017
2. Fire on board vehicle carrier honor. Accident no: DCA17RM007, National Transportation Safety Board Marine Accident Brief. Issued 6 Mar 2017
3. Fire aboard roll-on/roll-off vehicle carrier Höegh Xiamen, Pier 20, Blount Island Jacksonville, Florida June 4, 2020. National Transportation Safety Board, MAR 21/04. Adopted 1 Dec 2021
4. Fire spread in car parks. BRE Report BD2552, ISBN: 978 1 4098 2688 0, December 2010
5. Sprinklers controleren brand parkeergarage Epe. www.sprinkler.nl. Published 01 Sep 2020
6. Pichler D (2021) Elektroauto löst Feuer in Marienplatzgarage Ravensburg aus“, www.wochenblatt-news.de. Published 21 Nov 2021
7. BS EN 12845:2004 (2004) Fixed firefighting systems. Automatic sprinkler systems. Design, installation and maintenance. British Standards Institution, 2004
8. Crowder D (2009) Sprinkler protected car stacker fire test. Prepared for: The British Automatic Fire sprinkler Association, 11 December 2009, BRE Fire and Security, BRE Global, Client report number 256618
9. Brandversuche für Tiefgaragen (OH2) (Fire tests for underground car parks (OH2)) VdS Schadenverhütung. Dated 2 Jul 2004
10. Arvidson M, Släcksystem med vattendimma – en förnyad kunskapssammanställning, Brandforsk projekt 500-121. SP Report 2014:30, ISBN 978-91-87461-76-7
11. Arvidson M, Westlund Ö (2023) Water spray fire suppression tests comparing gasoline-fuelled and battery electric vehicles. Fire Technol. https://doi.org/10.1007/s10694-023-01473-w10.1007/s10694-023-01473-w ↗
12. MSC.1/Circ. 1430 (2012) Revised guidelines for the design and approval of fixed water-based fire-fighting systems for ro-ro spaces and special category spaces. International Maritime Organization, 31 May 2012
13. MSC.1/Circ.1430/Rev.1 (2018) Revised guidelines for the design and approval of fixed water-based fire-fighting systems for ro-ro spaces and special category spaces. International Maritime Organization, 7 December 2018
14. MSC.1/Circ.1430/Rev.2 (2020) Revised guidelines for the design and approval of fixed water-based fire-fighting systems for ro-ro spaces and special category spaces. International Maritime Organization, 8 December 2020
15. Arvidson M (2013) Large-scale water spray and water mist fire suppression system tests for the protection of ro-ro cargo decks on ships. Fire Technol. https://doi.org/10.1007/s10694-012-0312-710.1007/s10694-012-0312-7 ↗
16. NFPA 13 (2022) Standard for the installation of sprinkler systems, 2022 edition, National Fire Protection Association, 2022 edition, Quincy, USA
17. EN 12845:2015+A1:2019 (2019) Fixed firefighting systems. Automatic sprinkler systems. Design, installation and maintenance. European Committee for Standardization, 2019
18. FM Global Property Loss Prevention Data Sheets 3–26, Fire protection for nonstorage occupancies, April 2019, Interim Revision October 2021
19. Chatterjee P (2018) Sprinkler performance under non-sloped obstructed, ceiling construction. Research technical report, Project ID 0003059742, December 2018
20. Description of the development of automatic first response fire protection systems for ro-ro spaces on vehicle carriers. Deliverable D10.1, January 2022, The LASH FIRE Consortium, www.lashfire.eu