Numerical simulations are conducted to investigate the accuracy of the fire dynamics simulator (FDS 6.0.1) for under-ventilated enclosure fires with external flaming. The accuracy is discussed first in terms of mass balance at the steady-state stage for the enclosure volume. The required fineness of the grid is determined by analyzing the mass balance using two non-dimensional length scales. The first considers the ratio of the ventilation factor to the grid cell size, and the second considers the ratio of the hydraulic diameter of the opening to the grid cell size. When these two length scales are larger than 10, the corresponding mass balance error as obtained from post-processing the output is lower than 4%. The simulation results, including flow through the vertical opening, heat release rate inside the enclosure, gas temperature inside the enclosure, neutral plane height, and external flame height are compared with experimental data and empirical correlations. The air inflow rate through the opening is found to correlate linearly to the ventilation factor as $$ \dot{m} = 0.41 \cdot A\sqrt H $$ . For the heat release rate inside the enclosure, the predictions follow the empirical correlation $$ \dot{Q}in = 1131 \cdot A\sqrt H $$ . This is directly related to the air inflow rate and incomplete combustion with the inflowing oxygen. Time-averaged gas temperatures inside the enclosure are under-predicted by maximum 13.1% compared with experimental data at the corner near the opening. Neutral plane height values at the opening, determined from the velocity profile of the vent flow, show good agreement with empirical estimations ( $$ Zf = 0.4 \cdot H $$ ). Two methods are employed to determine the external flame height, namely a temperature based method and a volume heat release rate based method. The trends are captured correctly.
Source: openaire · Quality: candidate unverified · Source record ↗

Research context

OpenAlex topics: Fire dynamics and safety research · Evacuation and Crowd Dynamics · Fire effects on ecosystems

SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.

References (48)

Show source-provided references
1. Drysdale D (2011) An introduction to fire dynamics, 3rd edn, Wiley, New York10.1002/9781119975465 ↗
2. Bullen ML, Thomas PH (1979) Compartment fires with non-cellulosic fuels. In: 17th symposium (international) on combustion, The combustion Institute, Pittsburgh, pp 1139–1148.10.1016/S0082-0784(79)80108-3 ↗
3. Kawagoe K (1958) Fire behaviour in rooms. Report of the building research institute, Japan, No 27
4. Harmathy TZ (1972) A new look at compartment fires. Fire Technol 8(3):196–21710.1007/BF02590544 ↗
5. Thomas PH, Heselden AJM (1972) Fully developed fires in single compartments, CIB Report No 20. Fire Research Note 923, Fir Research Station, Borehamwood, England
6. Lee YP, Delichatsios MA, Silcock G (2007) Heat fluxes and flame heights in facades from fires in enclosures of varying geometry. Proc Combust Inst 31:2521–252810.1016/j.proci.2006.08.033 ↗
7. Lee YP (2006) Heat Fluxes and Flame Heights in External Façade Fires, Ph.D. thesis, University of Ulster, Fire SERT
8. Tang F, Hu LH, Delichatsios MA, Lu KH (2012) Experimental study on the flame height and temperature profile of buoyant window spill plume from an under-ventilated compartment fire. Int J Heat Mass Transf 55:93–10110.1016/j.ijheatmasstransfer.2011.08.045 ↗
9. Asimakopoulou EK, Kolaitis DI, Founti MA (2015) An experimental and numerical investigation of externally venting flames developing in an under-ventilated fire compartment-façade configuration. In: Proceedings of the European combustion meeting 2015.
10. Fleischmann CM, Parkes AR (1997) Effect of ventilation on the compartment enhanced mass loss rate. In: Fire safety journal proceedings of the fifth international symposium, pp 415–426.10.3801/IAFSS.FSS.5-415 ↗
11. Delichatsios MA, Silcock WH, Liu X, Delichatsios MM, Lee YP (2004) Mass pyrolysis rates and excess pyrolysate in fully developed enclosure. Fire Saf J 39:1–2110.1016/j.firesaf.2003.07.006 ↗
12. Babrauskas V, Williamson RB (1978) Post-flashover compartment fires: basis of a theoretical model. Fire Mater 2:39–5310.1002/fam.810020202 ↗
13. Quintiere JG, DenBraven K (1978). Some theoretical aspects of fire induced flows through doorways in a room-corridor scale model. NBSIR 78–1512.
14. Prahl J, Emmons HW (1975). Fire induced flow through an opening. Combust Flame 25:369–385.10.1016/0010-2180(75)90109-1 ↗
15. Rockett JA (1976). Fire induced gas flow in an enclosure, Combust Sci Technol 12:165–175.10.1080/00102207608946717 ↗
16. Thomas PH, Heselden AJM (1972). Fully Developed Fires in Single Compartments. Fire Research Note No.923. Fire Research Station, Borehamwood, England.
17. Tanaka T, Nakaya I, Yoshida M (1985) Full scale experiments for determining the burning conditions to be applied to toxicity tests. In: Proceedings of the first international symposium on fire safety science, pp 129–38
18. Suard S, Koched A, Pretrel H, Audouin L (2015). Numerical simulations of fire-induced doorway flows in a small scale enclosure. Int J Heat Mass Transf 81:578–590.10.1016/j.ijheatmasstransfer.2014.10.069 ↗
19. Stavrakakis GM, Markatos NC (2009). Simulation of airflow in one and two room enclosures containing a fire source. Int J Heat Mass Transf 52(11–12):2690–270310.1016/j.ijheatmasstransfer.2007.10.046 ↗
20. Wang L, Lim J, Quintiere JG (2011). On the prediction of fire-induced vent flows using FDS. J Fire Sci 30:110–121.10.1177/0734904111424562 ↗
21. Chow WK, Zou GW (2005). Correlation equations on fire-induced air flow rates through doorway derived by large eddy simulation. Build Environ, 40:897–906.10.1016/j.buildenv.2004.09.010 ↗
22. Pretrel H, Koched A, Audouin L (2015) Doorway flows induced by the combined effects of natural and forced ventilation in case of multi-compartments large-scale fire experiments. Fire Technol 1–26.
23. McGrattan K, Klein B, Hostikka S, Floyd J (2012) Fire dynamics simulator (version6), Users’ Guide, National Institute of Standards and Technology Report NIST special publication
24. McGrattan K, Klein B, Hostikka S, Floyd J (2012) Fire dynamics simulator (version6), technical reference guide, National Institute of Standards and Technology Report NIST special publication10.6028/NIST.SP.1018e6 ↗
25. DiNenno PJ, et al. (Eds) SFPE Handbook of fire protection engineering, Chapter 6, Section 3, 2nd edn, 3, pp 134–147
26. Babrauskas VA (1981) Closed-form approximation for post-flashover compartment fire temperatures. Fire Saf J 4:63–7310.1016/0379-7112(81)90005-9 ↗
27. Floyd J, McGrattan K Validation of a CFD fire model using two step combustion chemistry using the NIST reduced-scale ventilation-limited compartment data, fire safety science. In: Proceedings of the ninth international symposium, pp 117–128.10.3801/IAFSS.FSS.9-117 ↗
28. Tanga F, Hua LH (2012) Experimental study on flame height and temperature profile of buoyant window spill plume from an under-ventilated compartment fire. Int J Heat Mass Transf 55(1–3):93–101.10.1016/j.ijheatmasstransfer.2011.08.045 ↗
29. Hu Z, Utiskul Y, Quintiere JG (2007) Towards large eddy simulations of flame extinction and carbon monoxide emission in compartment fires. Proc Combust Inst 31:2537–254510.1016/j.proci.2006.08.053 ↗
30. Lecoustre V, Narayanan P, Baum HR, Trouve A (2011) Local extinction of diffusion flames in fires. Fire Saf Sci 10:583–59510.3801/IAFSS.FSS.10-583 ↗
31. Audouin L, Kolb G, Torero JL, Most JM (1995) Average centerline temperatures of a buoyant pool fire obtained by image processing of video recordings. Fire Saf J 24:167–18710.1016/0379-7112(95)00021-K ↗
32. Law M, O’Brien T (1989) Fire safety of bare external structural steel, The Steel Construction Institute, SCI Publication 009, U.K. ISBN: 0 86200 026 2.
33. Oleszkiewicz I (1989) Heat transfer from a window fire plume to a building façade. Am Soc Mech Eng Heat Transf Div 123:163–170.
34. Himotoa K, Tsuchihashib T, et al. (2009) Modeling the trajectory of window flames with regard to flow attachment to the adjacent wall. Fire Saf J 44(2):250–25810.1016/j.firesaf.2008.06.007 ↗
35. Goble K (2007) Height of flames projecting from compartment openings. Master thesis, University of Canterbury
36. Zhang J, Delichatsios MA, Colobert M, Hereid J (2008) Experimental and numerical investigations of heat impact and flame heights from fires in SBI tests. In: Fire safety science proceedings of the ninth international symposium, pp 205–21610.3801/IAFSS.FSS.9-205 ↗
37. Ma T, Quintiere JG (2001) Numerical Simulation of Axi-symmetric Fire Plumes: Accuracy and Limitations. MS Thesis, University of Maryland
38. Friday P, Mowrer FW (2001) Comparison of FDS model predictions with FM/SNL fire test data, NIST GCR 01-810. National Institute of Standards and Technology, Gaithersburg
39. McGrattan KB (2002) Improved radiation and combustion routines for a large eddy simulation fire model. In: Fire safety science, proceedings of the seventh international symposium, international association for fire safety science, WPI, Worcester, pp 827–838.
40. Bounagui A (2003) Simulation of the Fire for a Section of the L.H. La Fortaine Tunnel, IRC-RR- 140. National Research Council Canada, Ottawa
41. Grosshandle W (2005) Report of the technical investigation of the station night club fire, NIST NCSTAR 2, vol. 1, National Institute Standards and Technology, Gaithersburg
42. McGrattan KB, Baum HR, Rehm RG (1998) Large Eddy Simulations of Smoke Movement. Fire Fire Saf J 30(2):161–178.10.1016/S0379-7112(97)00041-6 ↗
43. Heskestad G (1999) Flame Heights of Fuel Arrays with Combustion in Depth, Fire Safety Science.In: Proceeding of the Fifth International Symposium, pp 427–438
44. Lock A, Bundy M, et al. (2008) Experimental study of the effects of fuel type, fuel distribution, and vent size on full-scale under-ventilated compartment fires in an ISO 9705 room. NIST Technical Note 1603, pp. 53–54
45. Cox G (eds) (1995) Basic considerations, in combustion fundamentals of fire. Academic Press, London, pp 1–30.
46. Orloff L, de Ris JN (1982) Froude modelling of pool fires. In: 19th Symposium (international) on combustion, The Combustion Institute, Pittsburgh, pp 885–89510.1016/S0082-0784(82)80264-6 ↗
47. Hasemi Y (1984) Experimental wall flame heat transfer correlations for the analysis of upward wall flame spread. Fire Sci Technol 4:75–9010.3210/fst.4.75 ↗
48. Quintiere J, Harkleroad M, Hasemi Y (1986) Wall flames and implications for upward flame spread. Combust Sci Technol 48(3–4):191–22210.1080/00102208608923893 ↗