Abstract

Twenty-two experiments have been conducted, with six different sloped roof vent areas, three fire source areas, and five door sizes, in a model-scale compartment with geometric dimensions of 150 cm length by 80 cm width by 150 cm height, to explore fire growth behavior and the temperature distribution in a compartment with a sloped roof vent (natural ventilation). It has been found in the experiments that, with increase of the sloped roof vent area, the maximum mass burning rate decreases gradually and the total combustion duration increases, in the condition of equal weight of total fuel in each test. This phenomenon demonstrates that the influence of the weakening effect owing to more energy loss via the roof vent is stronger than the strengthening effect due to combustion acceleration by enlarging the roof vent area, in the current experimental configuration. Moreover, the relationships between the average gas temperature rise and the roof vent area, as well as between the average gas temperature rise and the ratio of the roof vent area to total vent area, in the steady fire stage are summarized and quantified. In addition, it is found that, even when the roof vent area reaches 6.7 % of the floor area, the smoke layer height descends quickly, which poses a challenge to human evacuation.
Source: openaire · Quality: candidate unverified · Source record ↗

Research context

OpenAlex topics: Fire dynamics and safety research · Evacuation and Crowd Dynamics · Fire effects on ecosystems

SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.

References (8)

Show source-provided references
1. Utiskul Y, Quintiere JG, Rangwala AS, Ringwelski BA, Wakatsuki K, Naruse T (2007) Compartment fire phenomena under limited ventilation. Fire Saf J 40:367–39010.1016/j.firesaf.2005.02.002 ↗
2. Yii EH, Fleischmann CM, Buchanan AH (2005) Experimental study of fire compartment with door opening and roof opening. Fire Mater 29:315–33410.1002/fam.888 ↗
3. Fu Z, Hadjisophocleous G (2000) A two-zone fire growth and smoke movement model for multi-compartment buildings. Fire Saf J 34:257–28510.1016/S0379-7112(99)00045-4 ↗
4. Kumar R, Naveen M (2007) An experimental fire in compartment with dual vent on opposite walls. Combust Sci Technol 179:1527–154710.1080/00102200701202650 ↗
5. Merci B, Vandevelde P (2007) Experimental study of natural roof ventilation in full-scale enclosure fire tests in a small compartment. Fire Saf J 42:523–53510.1016/j.firesaf.2007.02.003 ↗
6. Merci B, Van Maele K (2008) Numerical simulations of full-scale enclosure fires in a small compartment with natural roof ventilation. Fire Saf J 43:495–51110.1016/j.firesaf.2007.12.003 ↗
7. Chen A, Francis J, Dong X, Chen W (2011) An experimental study of the rate of gas temperature rise in enclosure fires. Fire Saf J 46:397–40510.1016/j.firesaf.2011.06.006 ↗
8. Tang F, Hu LH, Delichatsios MA, Lu KH, Zhu W (2012) Experimental study on flame height and temperature profile of buoyant window spill plume from an under-ventilated compartment fire. Int J Heat Mass Transf 55:93–10110.1016/j.ijheatmasstransfer.2011.08.045 ↗