journal article·2019-03-06Open access

DC-Link Voltage Control of a Grid-Connected Solar Photovoltaic System for Fault Ride-Through Capability Enhancement

S. Raja Mohamed, P. Aruna Jeyanthy, D. Devaraj, M. H. Shwehdi, Adel Aldalbahi

Applied Sciences· Volume 9· Issue 5

Abstract

The high penetration level of solar photovoltaic (SPV) generation systems imposes a major challenge to the secure operation of power systems. SPV generation systems are connected to the power grid via power converters. During a fault on the grid side; overvoltage can occur at the direct current link (DCL) due to the power imbalance between the SPV and the grid sides. Subsequently; the SPV inverter is disconnected; which reduces the grid reliability. DC-link voltage control is an important task during low voltage ride-through (LVRT) for SPV generation systems. By properly controlling the power converters; we can enhance the LVRT capability of a grid-connected SPV system according to the grid code (GC) requirements. This study proposes a novel DCL voltage control scheme for a DC–DC converter to enhance the LVRT capability of the two-stage grid-connected SPV system. The control scheme includes a “control without maximum power point tracking (MPPT)” controller; which is activated when the DCL voltage exceeds its nominal value; otherwise, the MPPT control is activated. Compared to the existing LVRT schemes the proposed method is economical as it is achieved by connecting the proposed controller to the existing MPPT controller without additional hardware or changes in the software. In this approach, although the SPV system will not operate at the maximum power point and the inverter will not face any over current challenge it can still provide reactive power support in response to a grid fault. A comprehensive simulation was carried out to verify the effectiveness of the proposed control scheme for enhancing the LVRT capability and stability margin of an interconnected SPV generation system under symmetrical and asymmetrical grid faults.
Source: crossref · Quality: baseline

Research context

OpenAlex topics: Microgrid Control and Optimization · Photovoltaic System Optimization Techniques · Smart Grid Energy Management

SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.

Affiliations

Department of Electrical Engineering, King Faisal University, Hofuf 31982, Saudi Arabia

Department of Electrical Engineering, Kalasalingam Academy of Research and Education, Krishnan Koil 626126, India

Funding

Deanship of Scientific Research, King Faisal University

References (33)

Show source-provided references
1. Messenger, R., and Ventre, J. (2010). Photovoltaic Systems Engineering, CRC Press. [3rd ed.].
2. Control scheme for photovoltaic three-phase inverters to minimize peak currents during unbalanced grid-voltage sags10.1109/TPEL.2012.2191306 ↗
3. Benchmarking of grid fault modes in single-phase grid-connected photovoltaic systems10.1109/TIA.2013.2260512 ↗
4. Marinopoulos, A., Papandrea, F., Reza, M., Norrga, S., Spertino, F., and Napoli, R. (2011, January 19–23). Grid integration aspects of large solar PV installations: LVRT capability and reactive power/voltage support requirements. Proceedings of the 2011 IEEE Trondheim PowerTech, Trondheim, Norway.10.1109/PTC.2011.6019324 ↗
5. Modeling and control of grid-connected photovoltaic power plant with fault ride-through capability
6. LVRT of grid -connected PV system with energy storage
7. Hossain, M.K., and Ali, M.H. (2004, January 14–16). Low voltage ride through capability enhancement of grid connected PV system by SDBR. Proceedings of the IEEE PES T&D Conference and Exposition, Chicago, IL, USA.
8. Sabir, A. (2018). A novel low-voltage ride-through capable energy management scheme for a grid-connected hybrid photovoltaic-fuel cell power source. Int. Trans. Electr. Energy Syst., e2713.10.1002/etep.2713 ↗
9. Low voltage ride-through capability improvement of photovoltaic systems using a novel hybrid control10.1063/1.5005552 ↗
10. Ou, T.C., Lu, K.H., and Huang, C.J. (2017). Improvement of transient stability in a hybrid power multi-system using a designed NIDC (Novel Intelligent Damping Controller). Energies, 10.10.3390/en10040488 ↗
11. Wu, Y.-S., Chang, C.-H., Chen, Y.-M., Cheng, C.-S., Liu, C.-W., and Chang, Y.-R. (2012, January 4–6). The current control of PV inverter for low voltage ride through. Proceedings of the 15th International Power Electronics and Motion Control Conference, Novi Sad, Serbia.10.1109/EPEPEMC.2012.6397396 ↗
12. Implemental control strategy for grid stabilization of grid-connected PV system based on German grid code in symmetrical low-to-medium voltage network10.1109/TEC.2013.2263885 ↗
13. An advanced control strategy of PV system for low-voltage ride-through capability enhancement10.1016/j.solener.2014.08.018 ↗
14. Park, S.M., and Park, S.Y. (2013, January 17–21). Power weakening control of the photovoltaic-battery system for seamless energy transfer in micro grids. Proceedings of the IEEE Applied power electronics Conference and exposition long beach, Long Beach, CA, USA.10.1109/APEC.2013.6520721 ↗
15. Nezhad, A.A., Zaker, B.A., Arani, A.K., and Gharehpetian, G.B. (2017, January 19–20). Impact of non-MPPT operation mode of PV system considering inverter fault current limiting. Proceedings of the Conference on Electrical Power Distribution Networks Conference, Semnan, Iran.10.1109/EPDC.2017.8012739 ↗
16. Bak, Y., Lee, J.S., and Lee, K.B. (2018). Low-voltage ride-through control strategy for a grid-connected energy storage system. Appl. Sci., 8.10.3390/app8010057 ↗
17. Improvement of PV grid-tied inverters operation under asymmetrical fault conditions10.1016/j.solener.2016.04.015 ↗
18. Development of intelligent MPPT (maximum power point tracking) control for a grid-connected hybrid power generation system10.1016/j.energy.2012.12.017 ↗
19. Dynamic operation and control of micro grid hybrid power systems10.1016/j.energy.2014.01.042 ↗
20. A current limiting strategy to improve fault ride-through of inverter interfaced autonomous micro grids10.1109/TSG.2016.2517201 ↗
21. Perera, B.K., Ciufo, P., and Perera, S. (2013, January 10–13). Point of common coupling voltage control of a grid-connected solar photovoltaic (PV) system. Proceedings of the 39th Annual Conference of the IEEE Industrial Electronics Society, Vienna, Austria.10.1109/IECON.2013.6700377 ↗
22. A novel unsymmetrical faults analysis for microgrid distribution systems10.1016/j.ijepes.2012.05.012 ↗
23. Ground fault current analysis with a direct building algorithm for microgrid distribution10.1016/j.ijepes.2013.06.005 ↗
24. Boujelben, N., Masmoudi, F., Djemel, M., and Derbel, N. (2017, January 28–31). Design and comparison of quadratic boost and double cascade boost converters with boost converter. Proceedings of the 2017 14th International Multi-Conference on Systems, Signals & Devices (SSD), Marrakech, Morocco.10.1109/SSD.2017.8167022 ↗
25. Mousavi, M., Shabestari, P.M., and Mehrizi-Sani, A. (2018, January 21–23). Analysis and output voltage control of a high-efficiency converter for DC Micro grids. Proceedings of the IECON-44th annual conference of the IEEE Industrial Electronics Society, Washington, DC, USA.10.1109/IECON.2018.8591652 ↗
26. Mousa, M., Ahmed, M., and Orabi, M. (December, January 29). A switched inductor multilevel boost converter. Proceedings of the 2010 IEEE International Conference on Power and Energy, Kuala Lumpur, Malaysia.10.1109/PECON.2010.5697692 ↗
27. Single-and two-stage inverter-based grid-connected photovoltaic power plants with ride-through capability under grid faults10.1109/TSTE.2014.2347044 ↗
28. Máthé, L., Séra, D., and Kerekes, T. (2017). Three-phase photovoltaic systems: Structures, topologies, and control. Renewable Energy Devices and Systems with Simulations in Matlab® and Ansys, CRC Press.
29. Transient stability augmentation of PV/DFIG/SG–based hybrid power system by the parallel-resonance bridge fault current limiter10.1016/j.epsr.2015.08.016 ↗
30. E.ON-Netz (2019, February 01). Grid Code. Available online: http://www.eon-netz.com/.
31. Islam, S., Zeb, K., Din, W., Khan, I., Ishfaq, M., Busarello, T., and Kim, H. (2018). Design of a Proportional Resonant Controller with Resonant Harmonic Compensator and Fault Ride Trough Strategies for a Grid-Connected Photovoltaic System. Electronics, 7.10.3390/electronics7120451 ↗
32. Shafiul Alam, M., and Abido, M.A. (2017). Fault ride-through capability enhancement of voltage source converter-high voltage direct current systems with bridge type fault current limiters. Energies, 10.10.3390/en10111898 ↗
33. Low Voltage Ride through Control Capability of a Large Grid Connected PV System Combining DC Chopper and Current Limiting Techniques10.4236/jpee.2019.71004 ↗