journal article·2020-10-18Open access

Improved Control Strategy of MMC–HVDC to Improve Frequency Support of AC System

Zicong Zhang, Junghun Lee, Gilsoo Jang

Applied Sciences· Volume 10· Issue 20

Abstract

With the continuous development of power electronics technology, variable-speed offshore wind turbines that penetrated the grid system caused the problem of inertia reduction. This study investigates the frequency stability of synchronous, offshore wind-farm integration through a modular-multilevel-converter high-voltage direct-current (MMC–HVDC) transmission system. When full-scale converter wind turbines (type 4) penetrate the AC grid, the AC system debilitates, and it becomes difficult to maintain the AC system frequency stability. In this paper, we present an improved inertial-response-control method to solve this problem. The mathematical model of the synchronous generator is based on the swing equation and is theoretically derived by establishing a MMC–HVDC. Based on the above model, the inertia constant is analyzed using a model that integrates the MMC–HVDC and offshore synchronous generator. With the new improved control method, a more sensitive and accurate inertia index can be obtained using the formula related to the effective short-circuit ratio of the AC system. Moreover, it is advantageous to provide a more accurate inertial control evaluation for AC systems under various conditions. Furthermore, the impact of the MMC–HVDC on system safety is assessed based on the capacitor time constant. This simulation was implemented using the PSCAD/EMTDC platform.
Source: crossref · Quality: baseline

Research context

OpenAlex topics: HVDC Systems and Fault Protection · High-Voltage Power Transmission Systems · Microgrid Control and Optimization

SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.

Affiliations

Power and Energy Laboratory, School of Electrical Engineering, Korea University, Seoul 02841, Korea

Funding

Korea Institute of Energy Technology Evaluation and Planning

References (27)

Show source-provided references
1. Hertem, D.V., Gomis-Bellmunt, O., and Liang, J. (2016). HVDC Grids for Offshore and Supergrid of the Future, Wiley-IEEE Press.
2. Wind in weak grids: 4 Hz or 30 Hz Oscillations?10.1109/TPWRS.2018.2852947 ↗
3. Inertia-free stand-alone microgrid, part II: Inertia control for stabilizing DC-link capacitor voltage of PMSG wind turbine system10.1109/TIA.2018.2840083 ↗
4. Wind power plant level testing of inertial response with optimised recovery behaviour10.1049/iet-rpg.2018.5232 ↗
5. Wu, Q.W., and Sun, Y.Z. (2018). Modeling and Modern Control of Wind Power, Wiley-IEEE Press.10.1002/9781119236382 ↗
6. Frequency control design for offshore wind farm grid with LCC-HVDC link connection10.1109/TED.2008.916708 ↗
7. Wind farms with HVDC delivery in inertial response and primary frequency control10.1109/TEC.2010.2060202 ↗
8. Impact of inertia and effective short circuit ratio on control of frequency in weak grids interfacing LCC-HVDC and DFIG-based wind farms10.1109/TPWRD.2016.2607205 ↗
9. New insights into coupled frequency dynamics of AC grids in rectifier and inverter sides of LCC-HVDC interfacing DFIG-based wind farms10.1109/TPWRD.2017.2757399 ↗
10. Sha, J.B., Guo, C.Y., Rehman, A.U., and Zhao, C.Y. (2019). A Quantitative Index to Evaluate the Commutation Failure Probability of LCC-HVDC with a Synchronous Condenser. Appl. Sci., 9.10.3390/app9050925 ↗
11. Li, Y.Y., Liu, K.P., Liao, X.B., Zhu, S., and Huai, Q. (2019). A Virtual Impedance Control Strategy for Improving the Stability and Dynamic Performance of VSC–HVDC Operation in Bidirectional Power Flow Mode. Appl. Sci., 9.10.3390/app9153184 ↗
12. Stability analysis of a microgrid system with a hybrid offshore wind and ocean energy farm fed to a power grid through an HVDC Link10.1109/TIA.2017.2787126 ↗
13. Contribution of VSC-HVDC to frequency regulation of power systems with offshore wind generation10.1109/TEC.2015.2417130 ↗
14. Grid code compatibility of VSC-HVDC connected offshore wind turbines employing power synchronization control10.1109/TPWRS.2016.2515504 ↗
15. Power-synchronization control of grid-connected voltage-source converters10.1109/TPWRS.2009.2032231 ↗
16. Offshore wind integration to a weak grid by VSC-HVDC links using power-synchronization control: A case study10.1109/TPWRD.2013.2273979 ↗
17. Inertia emulation control strategy for VSC-HVDC transmission systems10.1109/TPWRS.2012.2213101 ↗
18. Control of VSC-HVDC connected offshore windfarms for providing synthetic inertia10.1109/JESTPE.2017.2751541 ↗
19. Synchronous generator emulation control strategy for voltage source converter (VSC) stations10.1109/TPWRS.2014.2384498 ↗
20. Hafeez, K., Khan, S.A., Van den Bossche, A., and Hasan, Q.A. (2019). Circulating Current Reduction in MMC-HVDC System Using Average Model. Appl. Sci., 9.10.3390/app9071383 ↗
21. Dynamic averaged and simplified models for MMC-based HVDC transmission Systems10.1109/TPWRD.2013.2251912 ↗
22. Efficient modeling of modular multilevel HVDC converters (MMC) on electromagnetic transient simulation programs10.1109/TPWRD.2010.2060737 ↗
23. Short-term frequency regulation and inertia emulation using an MMC-based MTDC system10.1109/TPWRS.2017.2757258 ↗
24. Inertia emulation and dynamic voltage support scheme for MMC-based dc systems10.1049/iet-rpg.2018.5264 ↗
25. Zhu, J.B., Shen, Z.P., Bu, S.Q., Li, X.L., Booth, C.D., Qiu, W., Jia, H.J., and Wang, C.S. (2020). Coordinated Flexible Damping Mechanism with Inertia Emulation Capability for MMC-MTDC Transmission Systems. IEEE J. Emerg. Sel. Top. Power Electron., 1–14.
26. Detailed and averaged models for a 401-level MMC-HVDC system10.1109/TPWRD.2012.2188911 ↗
27. D’Arco, S., Nguyen, T.T., and Suul, J.A. (2019, January 14–17). Evaluation of Virtual Inertia Control Strategies for MMC-based HVDC Terminals by P-HiL Experiments. In Proceeding of the IECON 2019—45th Annual Conference of the IEEE Industrial Electronics Society, Lisbon, Portugal.10.1109/IECON.2019.8927704 ↗