Low-Loss Active Grid Impedance Cancellation in Grid-Connected Inverters with LCL Filter
Source abstract
Abstract
Distributed power inverters with inductive capacitive–inductive (LCL) filters have become popular in distributed power generation system. However, due to unknown grid impedance, the inverters are confronted with challenges of local filter resonance, poor power quality, and multiple interactive resonance. This paper proposes a low-loss active compensator that can counteract effects of the grid impedance on the current control performance of single-phase grid-connected inverter with an LCL filter. The compensator utilizes dual unit point-of-common-coupling voltage feedforward control mechanisms (VFFC), in which one is integrated with the inverter controller, and the other is generated through an extra low voltage source converter (LV-VSC) in series with the filter capacitor. The LV-VSC has no additional passive inductive-capacitive filtering elements and provides very low volt-ampere. To confirm its validity, a single-phase inverter testbed integrated with the compensator was built. The experimental results validate the current-controlled performance enhancement of the proposed inverter system operating under different grid conditions.
Source: crossref · Quality: baseline
Research context
OpenAlex topics: Microgrid Control and Optimization · Islanding Detection in Power Systems · Advanced DC-DC Converters
SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.
Affiliations
College of Automation, Hangzhou Dianzi University, Hangzhou 310027, China
Funding
National Natural Science Foundation of China
References (37)
Show source-provided references
1. Grid current regulation of a three-phase voltage source inverter with an LCL input filter10.1109/TPEL.2003.810838 ↗
2. Digital Current Control of a Voltage Source Converter with Active Damping of LCL Resonance10.1109/TPEL.2006.880271 ↗
3. Analysis of the Passive Damping Losses in LCL-Filter-Based Grid Converters10.1109/TPEL.2012.2222931 ↗
4. A New Design Method for the Passive Damped LCL and LLCL Filter-Based Single-Phase Grid-Tied Inverter10.1109/TIE.2012.2217725 ↗
5. Optimal Design of High-Order Passive-Damped Filters for Grid-Connected Applications10.1109/TPEL.2015.2441299 ↗
6. Solid-State Single-Port Series Damping Device for Power Converters in DC Microgrid Systems10.1109/TPEL.2018.2811941 ↗
7. Tao, H., Zhou, Y., Zhang, G., and Zheng, Z. (2019). Parallel Resonance Mechanism Analysis and Suppression of Inductance-Capacitance-Inductance Grid-Connected Inverters. Energies, 12.10.3390/en12091656 ↗
8. Yang, L., Chen, Y., Wang, H., Luo, A., and Huai, K. (2018). Oscillation Suppression Method by Two Notch Filters for Parallel Inverters under Weak Grid Conditions. Energies, 11.10.3390/en11123441 ↗
9. Zhang, H., Kou, B., Zhang, L., and Jin, Y. (2016). Digital Controller Design Based on Active Damping Method of Capacitor Current Feedback for Auxiliary Resonant Snubber Inverter with LC Filter. Appl. Sci., 6.10.3390/app6110377 ↗
10. A Modified Direct Power Control Strategy Allowing the Connection of Three-Phase Inverters to the Grid through LCL Filters10.1109/TIA.2007.904438 ↗
11. Design Considerations of Digitally Controlled LCL-Filtered Inverter with Capacitor- Current-Feedback Active Damping10.1109/JESTPE.2014.2350262 ↗
12. Effect of Active Damping on Output Impedance of Three-Phase Grid-Connected Converter10.1109/TIE.2017.2696494 ↗
13. Virtual RC Damping of LCL-Filtered Voltage Source Converters with Extended Selective Harmonic Compensation10.1109/TPEL.2014.2361853 ↗
14. Regions of Active Damping Control for LCL Filters10.1109/TIA.2013.2266892 ↗
15. Design and Analysis of Robust Active Damping for LCL Filters Using Digital Notch Filters10.1109/TPEL.2016.2565598 ↗
16. Robust Active Damping Methods for LCL Filter-Based Grid-Connected Converters10.1109/TPEL.2016.2626290 ↗
17. An Efficient and Robust Hybrid Damper for LCL- or LLCL-Based Grid-Tied Inverter with Strong Grid-Side Harmonic Voltage Effect Rejection10.1109/TIE.2015.2478738 ↗
18. Investigation and Active Damping of Multiple Resonances in a Parallel-Inverter-Based Microgrid10.1109/TPEL.2012.2195032 ↗
19. Resonance Interaction of Multiparallel Grid-Connected Inverters with LCL Filter10.1109/TPEL.2016.2585547 ↗
20. An active damper for stabilizing power-electronics-based ac systems10.1109/TPEL.2013.2278716 ↗
21. An Adaptive Active Damper for Improving the Stability of Grid-Connected Inverters under Weak Grid10.1109/TPEL.2018.2793242 ↗
22. Middlebrook, R.D. (1976, January 11–14). Input filter considerations in design and application of switching regulators. Proceedings of the IEEE Industry Applications Society Annual Meeting, Chicago, IL, USA.
23. Impedance-Based Stability Criterion for Grid-Connected Inverters10.1109/TPEL.2011.2136439 ↗
24. Modeling and Analysis of Grid Harmonic Distortion Impact of Aggregated DG Inverters10.1109/TPEL.2010.2091286 ↗
25. Modeling and Control of N-Paralleled Grid-Connected Inverters with LCL Filter Coupled Due to Grid Impedance in PV Plants10.1109/TPEL.2010.2095429 ↗
26. Analysis of Current Control Interaction of Multiple Parallel Grid Connected Inverters
27. Suntio, T., Messo, T., Berg, M., Alenius, H., Reinikka, T., Luhtala, R., and Zenger, K. (2019). Impedance-Based Interactions in Grid-Tied Three-Phase Inverters in Renewable Energy Applications. Energies, 12.10.3390/en12030464 ↗
28. Damping Methods for Resonances Caused by LCL-Filter-Based Current-Controlled Grid-Tied Power Inverters: An Overview10.1109/TIE.2017.2714143 ↗
29. Benchmarking of Stability and Robustness against Grid Impedance Variation for LCL-Filtered Grid-Interfacing Inverters10.1109/TPEL.2017.2784685 ↗
30. Passivity-Based Controller Design of Grid-Connected VSCs for Prevention of Electrical Resonance Instability10.1109/TIE.2014.2336632 ↗
31. Full-Feedforward Schemes of Grid Voltages for a Three-Phase LCL-Type Grid-Connected Inverter10.1109/TIE.2012.2193864 ↗
32. Impedance Shaping of the Grid-Connected Inverter with LCL Filter to Improve Its Adaptability to the Weak Grid Condition10.1109/TPEL.2014.2300235 ↗
33. Capacitor-Voltage Feedforward with Full Delay Compensation to Improve Weak Grids Adaptability of LCL-Filtered Grid-Connected Converters for Distributed Generation Systems10.1109/TPEL.2017.2665483 ↗
34. Active Cancellation of Equivalent Grid Impedance for Improving Stability and Injected Power Quality of Grid-Connected Inverter under Variable Grid Condition10.1109/TPEL.2018.2793459 ↗
35. Power Factor Correction Using a Series Active Filter10.1109/TPEL.2004.839819 ↗
36. He, Y., Wang, K., and Chung, H.S.-H. (2014, January 14–18). Utilization of Proportional Filter Capacitor Voltage Feedforward to Realize Active Damping for Digitally-Controlled Grid-Tied Inverter Operating under Wide Grid Impedance Variation. Proceedings of the IEEE Energy Conversion Congress and Exposition (ECCE), Pittsburgh, PA, USA.10.1109/ECCE.2014.6953730 ↗
37. (2008). IEEE Standard for Interconnecting Distributed Resources with Electric Power Systems, IEEE. IEEE Application Guide for IEEE Std. 1547; IEEE Standard 1547.2-2008.