journal article·2022-01-21Open access

Seismic Response Analysis of High-Voltage Bushings and Down Lead Transmission Line Systems in Substations

Meng Zhang, Ran Wei, Yuanxiang Du, Guifeng Zhao

Applied Sciences· Volume 12· Issue 3

Abstract

Based on an actual ultra-high voltage (UHV) substation, a finite element (FE) model for a high-voltage (HV) bushing, arrester, and down lead transmission line (DLTL) system was built using ANSYS software. The dynamic responses of the system under different seismic intensities were analyzed and compared with those of the corresponding single bushing and arrester. On this basis, the coupling vibration influence of the upper DLTL on the responses of the HV bushing and arrester is discussed. The results indicate that the DLTL adversely affects the responses of the HV bushing and arrester under seismic loading. As the seismic intensity increases, the structural displacements at the top of the HV bushing and arrester increase, accompanied by a reduction in the geometric length redundancy of the DLTL, resulting in a mutual pulling effect between the HV bushing and the arrester and the quick amplification of their respective dynamic responses in a nonlinear form. Under the action of an earthquake with a peak ground acceleration (PGA) of 0.4 g, the maximum stresses at the roots of the HV bushing and the arrester in the system separately increase by approximately 13.02% and 7.80% compared to the corresponding single HV bushing and the arrester. Overall, a geometric length redundancy of at least 200 mm in the DLTL in engineering design is recommended.
Source: crossref · Quality: baseline

Research context

OpenAlex topics: Vibration and Dynamic Analysis · Geotechnical Engineering and Underground Structures · Seismic Performance and Analysis

SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.

Affiliations

School of Civil Engineering, Zheng Zhou University, Zhengzhou 450001, China

Funding

National Natural Science Foundation of China · Cultivating Fund Project for Young Teachers of Zhengzhou University

References (27)

Show source-provided references
1. Research on Operating and Control of the UHV Power Grid
2. Research state and development of seismic performance of substation electrical equipment
3. Research Progress in Prevention of Earthquake and Secondary Disasters on Power Facilities
4. Fujisaki, E., Takhirov, S., Xie, Q., and Mosalam, K.M. (July, January 30). Seismic Vulnerability of Power Supply: Lessons Learned from Recent Earthquakes and Future Horizons of Research. Proceedings of the 9th international conference on structural dynamics (EURODYN 2014), Porto, Portugal.
5. Effects of the January 2010 Haitian Earthquake on Selected Electrical Equipment10.1193/1.3636415 ↗
6. Performance of Electric Power Systems in the 2010–2011 Christchurch, New Zealand, Earthquake Sequence10.1193/022813EQS056M ↗
7. Seismic damage investigation and analysis of electric power system in Lushan Ms 7.0 earthquake
8. Damage Analysis of a Transformer Porcelain High Voltage Bushing in a Low Intensity Earthquake
9. Analysis on 220 KV Transformer Fault Caused by Sealing Failure of Bushing
10. Seismic evaluation and retrofit of 230-kV porcelain transformer bushings10.1193/1.1427316 ↗
11. Seismic Response of High Voltage Electrical Transformer–Bushing Systems10.1061/(ASCE)0733-9445(2006)132:2(287) ↗
12. Seismic Performance of Ultra High Voltage Gas Insulated Switchgear Porcelain Bushing
13. Earthquake Simulation Shaking Table Test for 1100 kV UHV Bushing
14. Considering seismic interaction effects in designing steel supporting structure for surge arrester10.1016/j.jcsr.2017.01.012 ↗
15. Seismic risk mitigation of cylindrical electrical equipment with a novel isolation device10.1016/j.soildyn.2018.04.001 ↗
16. Estimation of Displacement at Interconnection Points of Substation Equipment Subjected to Earthquakes10.1109/TPWRD.2003.823203 ↗
17. Seismic behavior of flexible conductors connecting substation equipment-part II: Shake table tests10.1109/TPWRD.2004.832387 ↗
18. Dynamic Interaction of High-Voltage Power Transformer Bushings, Turrets, and Tanks
19. Analysis of wind-induced response of down lead transmission line-connection fitting systems in ultrahigh-voltage substations10.1016/j.engstruct.2019.110144 ↗
20. Krawczuk, M., and Palacz, M. (2021). Special Issue “Applications of Finite Element Modeling for Mechanical and Mechatronic Systems”. Appl. Sci., 11.10.3390/app11115170 ↗
21. Loading noise effects on the system identification of composite structures by dynamic tests with vibrodyne10.1016/j.compositesb.2016.09.032 ↗
22. Dynamic crack growth based on moving mesh method10.1016/j.compositesb.2019.107053 ↗
23. Shang, R. (2020). Study on the Bearing Capacity of Down Lead Transmission Line-Connection Fitting and Bushing Systems under Dynamic Loads in Ultrahigh-Voltage Substations, Zhengzhou University.10.1016/j.engstruct.2019.110144 ↗
24. Shaking table test on seismic performance of large power transformer with bushings
25. Shake-table Test on Earthquake Simulation of Substation Equipment Interconnected by Flexible Bus
26. Ground motion amplification at flange level of bushings mounted on electric substation transformers10.1002/eqe.26 ↗
27. Study on Required Flexible Conductor Slack of Connecting High-voltage Electrical Equipment Under Earthquakes