journal article·2022-06-09Open access

Study on the Bending Stiffness of Joints Connecting Porcelain Bushings and Flanges in Ultra-High Voltage Electrical Equipment

Quanjun Zhu, Xingui Zhang, Zhengguo Gao

Applied Sciences· Volume 12· Issue 12

Abstract

In this study, the equivalent bending stiffness of cement-bonded joints connecting the porcelain bushing and flange in ultra-high voltage (UHV) electrical equipment was investigated. A mechanical bending model of the joint was developed based on its structural features, and a new equation for the equivalent bending stiffness of the joint was proposed. Based on experimental data for nine UHV porcelain bushings, a dimensionless elasticity coefficient for the equivalent bending stiffness equation was determined. Finally, considering two 1000 kV arresters as examples, the bending stiffness was calculated using the equation proposed in this paper and that which is used in China’s seismic code. A comparison of the results shows that the equation proposed in this study is in better agreement with the experimental data. Compared with the code equation, the equation in this paper adopts the expression for the dimensionless coefficient, which can more reasonably reveal the bending mechanism of the joint.
Source: crossref · Quality: baseline

Research context

OpenAlex topics: Vibration and Dynamic Analysis · Seismic Performance and Analysis · Structural Engineering and Vibration Analysis

SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.

Affiliations

Global Energy Interconnect Research Institute, Beijing 102211, China

School of Transportation Science and Engineering, Beihang University, Beijing 100191, China

Funding

Science and Technology Project of SGCC

References (25)

Show source-provided references
1. Liu, R., Zhang, M., and Wu, Y. (2012, January 24–28). Vulnerability study of electric power grid in different intensity area in Wenchuan earthquake. Proceedings of the 15th World Conference of Earthquake Engineering (WCEE), Lisboa, Portugal.
2. Johnson, F., and Iliev, K. (2012, January 22–26). Earthquake effects on SDG&E’s 500/230 kV Imperial Valley Substation. Proceedings of the 2012 IEEE Power and Energy Society General Meeting, San Diego, CA, USA.10.1109/PESGM.2012.6345210 ↗
3. Tang, A.K., and Eidinger, J.M. (2013). Chile Earthquake of 2010: Lifeline Performance, American Society of Civil Engineers.10.1061/9780784412824 ↗
4. Seismic damage investigation and analysis of electric power system in Lushan Ms 7.0 earthquake
5. Weibull distribution based seismic vulnerability analysis of porcelain equipment
6. Study of seismic response and vibration control of High voltage electrical equipment damper based on TMD
7. Evaluation of power substation equipment seismic vulnerability by multivariate fragility analysis: A case study on a 420 kV circuit breaker10.1016/j.soildyn.2016.09.026 ↗
8. On the Nonlinear Seismic Responses of Shock Absorber-Equipped Porcelain Electrical Components10.1155/2020/9026804 ↗
9. Review on seismic disaster analysis and aseismatic measures of transformer substation
10. Tests and Analyses on Failure Mechanism of 1100 kV UHV Transformer Porcelain Bushing
11. Seismic failure probability of a 400 kV power transformer using analytical fragility curves10.1016/j.engfailanal.2016.09.007 ↗
12. Analysis of dynamic characteristics of structural joints using stiffness influence coefficients10.1007/BF03191916 ↗
13. Analysis and design of the prototype of a steel 1-MW wind turbine tower10.1016/S0141-0296(03)00059-2 ↗
14. Comparative study on porcelain insulators design for high-voltage electric equipment at home and abroad
15. (2013). Code for Seismic Design of Electrical Installations (Standard No. GB 50260-2013).
16. (1984). Seismic Design Guidelines for Electrical Equipment (Standard No. JEAG 5003-1980).
17. Study of seismic performance and damping effects of porcelain column circuit breaker SF6
18. Experimental study of the bending rigidity at flange connection of UHV electrical equipment
19. Earthquake simulation shaking table test for 1100 kV UHV bushing
20. Influence of flange on seismic performance of 1100-kV ultra-high voltage transformer bushing10.1193/122517EQS266M ↗
21. Study on seismic performance of porcelain pillar electrical equipment based on nonlinear dynamic theory10.1155/2021/8816322 ↗
22. Coefficient of bending stiffness of interconnected parts between ultra-high voltage porcelain bushings and flanges
23. Gao, Z., Zhu, Q., Yang, Q., and Cao, M. (2018). Study on Bending Stiffness of Interconnected Part Between High Voltage Porcelain Bushing and Flange. Insul. Surge Arresters, 184–189.
24. Huang, Y., Zhao, X., and Chen, S. (1996). Rayleigh-Ritz method in elastic dynamics. J. Hebei Inst. Technol., 62–66. Available online: https://kns.cnki.net/kcms/detail/detail.aspx?dbcode=CJFD&dbname=CJFD9697&filename=HBLG602.018&uniplatform=NZKPT&v=nRFEvR5lgf9x5s968OncmtSvruS1JJFee2xGtiymIbClVnp-stTT1udqFdUKqRFA.
25. Zhang, P. (2010). Energy Theory in Structural Mechanics, Shanghai Scientific and Technical Publishers.