Modeling and Performance Analysis of a Pump-Driven Chip-Level Two-Phase Cooling System in Data Centers
Source abstract
Abstract
As a powerful solution for heat dissipation in data centers, chip-level cooling continues to capture escalating attention in research and application domains. To accurately analyze system performance, identify potential avenues for system optimization, and inform future practical applications, we developed a steady-state, one-dimensional mathematical model for a novel pump-driven chip-level two-phase cooling system (PCTCS). This model was constructed based on our previous study and was confirmed against existing experimental data. Our simulations scrutinized PCTCS performance under default conditions and investigated the effects of key parameters, such as refrigerant type, condenser vertical positioning, and cooling water temperature. Results showed that the system could manage an 80 W power output from each CPU while maintaining CPU temperatures around 79 °C at a cooling water temperature of 45 °C. We discovered the choice of refrigerant had a significant impact on performance, with R32 outperforming R134a and R113. While the vertical position of the condenser influenced the PCTCS’s internal parameters, its overall impact on system performance was negligible. Moreover, provided the chip temperature remained within a safe range, our study found that increasing the cooling water temperature improved the energy efficiency ratio of the refrigerant pump and reduced the temperature difference between the chips and the cold source.
Source: crossref · Quality: baseline
Research context
OpenAlex topics: Heat Transfer and Boiling Studies · Heat Transfer and Optimization · Refrigeration and Air Conditioning Technologies
SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.
Affiliations
School of Aeronautical Science and Engineering, Beihang University, Beijing 100191, China
Aeronautic Institute of Xiangyang, Xiangyang 441000, China
Department of Building Science, School of Architecture, Tsinghua University, Beijing 100084, China
References (49)
Show source-provided references
1. A review on airflow distribution and management in data center10.1016/j.enbuild.2018.08.050 ↗
2. Xu, S., Zhang, H., and Wang, Z. (2023). Thermal Management and Energy Consumption in Air, Liquid, and Free Cooling Systems for Data Centers: A Review. Energies, 16.10.3390/en16031279 ↗
3. The role of data centres in the future Danish energy system10.1016/j.energy.2020.116928 ↗
4. Recalibrating global data center energy-use estimates10.1126/science.aba3758 ↗
5. Research and Technologies for next-generation high-temperature data centers—State-of-the-arts and future perspectives10.1016/j.rser.2022.112991 ↗
6. Data center power requirements: Measurements from Silicon Valley10.1016/S0360-5442(03)00009-4 ↗
7. Influence of cooling architecture on data center power consumption10.1016/j.energy.2019.06.140 ↗
8. Study on influence of operating parameters of data center air conditioning system based on the concept of on-demand cooling10.1016/j.renene.2020.06.100 ↗
9. Simulation study on performance of data center air-conditioning system with novel evaporative condenser10.1016/j.energy.2020.118521 ↗
10. A review of thermal management and innovative cooling strategies for data center
11. A review of current status of free cooling in datacenters10.1016/j.applthermaleng.2016.10.093 ↗
12. Sustainability analysis of zero energy consumption data centers with free cooling, waste heat reuse and renewable energy systems: A feasibility study10.1016/j.energy.2022.125495 ↗
13. Experimental investigation of hydrothermal characteristics of data center servers’ liquid cooling system for different flow configurations and geometric conditions10.1016/j.csite.2021.101276 ↗
14. Li, L., Zheng, W., Wang, X., and Wang, X. (2014, January 18–20). Coordinating liquid and free air cooling with workload allocation for data center power minimization. Proceedings of the 11th International Conference on Autonomic Computing ({ICAC} 14), Philadelphia, PA, USA.
15. Joshi, Y., and Kumar, P. (2012). Energy Efficient Thermal Management of Data Centers, Springer Science & Business Media.10.1007/978-1-4419-7124-1 ↗
16. Cooling of server electronics: A design review of existing technology10.1016/j.applthermaleng.2016.03.056 ↗
17. A Review on efficient thermal management of air- and liquid-cooled data centers: From chip to the cooling system10.1016/j.apenergy.2017.08.037 ↗
18. Flow Boiling of R134a in a Multi-Microchannel Heat Sink With Hotspot Heaters for Energy-Efficient Microelectronic CPU Cooling Applications10.1109/TCPMT.2011.2123895 ↗
19. Experimental evaluation of a controlled hybrid two-phase multi-microchannel cooling and heat recovery system driven by liquid pump and vapor compressor10.1016/j.ijrefrig.2012.11.011 ↗
20. A review of on-chip micro-evaporation: Experimental evaluation of liquid pumping and vapor compression driven cooling systems and control10.1016/j.apenergy.2011.10.030 ↗
21. Data center energy conservation study utilizing loop heat pipes as a chip-level cooling technique and its industrial application10.1016/j.applthermaleng.2022.119715 ↗
22. Fluidic rolling robot using voltage-driven oscillating liquid10.1088/1361-665X/ac895a ↗
23. Modeling and performance analysis of a two-phase thermosyphon loop with partially/fully liquid-filled downcomer10.1016/j.ijrefrig.2015.06.014 ↗
24. Marcinichen, J.B., and Thome, J.R. (2010, January 14–17). New novel green computer two-phase cooling cycle: A model for its steady-state simulation. Proceedings of the Proceedings of the 23rd International Conference on Efficiency, Cost, Optimization, Simulation and Environmental Impact of Energy Systems-ECOS2010, Lausanne, Switzerland.
25. Ong, C.L., Amalfi, R.L., Marcinichen, J.B., Lamaison, N., and Thome, J.R. (September, January 29). Two-phase mini-thermosyphon for cooling of datacenters: Experiments, modeling and simulations. Proceedings of the International Electronic Packaging Technical Conference and Exhibition, San Francisco, CA, USA.
26. Review of recent developments on pump-assisted two-phase flow cooling technology10.1016/j.applthermaleng.2018.12.169 ↗
27. Wang, L., Yang, T., Yuana, W., and Ren, K. (2023). Experimental study of pump-driven chip-level two-phase cooling system for data centres. Indoor Built Environ., accepted.10.1177/1420326X231183300 ↗
28. Brown, G.O. (2003). Environmental and Water Resources History, American Society of Civil Engineers.
29. A review of heat transfer and pressure drop characteristics of single and two-phase microchannels10.1016/j.ijheatmasstransfer.2014.07.090 ↗
30. A simple friction pressure drop correlation for two-phase flow in pipes10.1016/0255-2701(86)80008-3 ↗
31. Tahery, R., and Ehterami, S. (2011, January 21–24). Two-phase Frictional Pressure Drop in Horizontal Channels. Proceedings of the 7th International Chemical Engineering Congress & Exhibition (IChEC 2011), Kish, Iran.
32. An analysis of experimental data and prediction methods for two-phase frictional pressure drop and flow boiling heat transfer in micro-scale channels10.1016/j.expthermflusci.2006.01.006 ↗
33. Void fractions in two-phase flow: A correlation based upon an equal velocity head model10.1243/PIME_PROC_1969_184_051_02 ↗
34. Shah, R., and London, A.L. (1978). Laminar Flow Forced Convection in Ducts, Supplement 1 to Advances in Heat Transfer, Academic Press.10.1016/B978-0-12-020051-1.50006-1 ↗
35. New equations for heat and mass transfer in turbulent pipe and channel flow
36. Subramanian, R.S. (2015). Heat Transfer in Flow through Conduits, Department of Chemical and Biomolecular Engineering, Clarkson University Project.
37. An Extension of the Flow Boiling Correlation to Transition, Laminar, and Deep Laminar Flows in Minichannels and Microchannels10.1080/01457630490280425 ↗
38. A general correlation for saturated two-phase flow boiling heat transfer inside horizontal and vertical tubes10.1115/1.2910348 ↗
39. A model for predicting the two-phase flow boiling heat transfer coefficient in augmented tube and compact heat exchanger geometries10.1115/1.2911229 ↗
40. Heat transfer characteristics in partial boiling, fully developed boiling, and significant void flow regions of subcooled flow boiling10.1115/1.2824263 ↗
41. Development of a flow boiling map for subcooled and saturated flow boiling of different fluids inside circular tubes10.1115/1.2910524 ↗
42. Saha, P., and Zuber, N. (1974, January 3–7). Point of net vapor generation and vapor void fraction in subcooled boiling. Proceedings of the International Heat Transfer Conference Digital Library, Tokyo, Japan.10.1615/IHTC5.430 ↗
43. A new computational procedure for refrigerant condensation inside herringbone-type Brazed Plate Heat Exchangers10.1016/j.ijheatmasstransfer.2014.11.032 ↗
44. A survey of correlations for heat transfer and pressure drop for evaporation and condensation in plate heat exchangers10.1016/j.ijrefrig.2015.11.013 ↗
45. Lemmon, E., Huber, M.L., and McLinden, M.O. (2007). NIST Standard Reference Database 23: Reference Fluid Thermodynamic and Transport Properties-REFPROP, Version 8.0.
46. Choosing working fluid for two-phase thermosyphon systems for cooling of electronics10.1115/1.1571570 ↗
47. Effect of condenser location and imposed circulation on the performance of a compact two-phase thermosyphon10.1080/10893950390203341 ↗
48. Cooling performance of a pump-driven two phase cooling system for free cooling in data centers10.1016/j.applthermaleng.2015.11.002 ↗
49. Performance of a R-134a-filled thermosyphon10.1016/S1359-4311(03)00207-2 ↗