Stability Comparison of Grid-Connected Inverters Considering Voltage Feedforward Control in Different Domains
Source abstract
Abstract
Under the background of high permeability, voltage feedforward control may further weaken the stability of grid-connected inverter (GCI) systems and may cause sub-synchronous oscillation in extreme cases. To solve this problem, this paper firstly considers the influence of the frequency coupling effect and voltage feedforward control, and adopts the harmonic linearization method to construct the L-type GCI sequence admittance model with PI (proportional integral) control and PR (proportional resonant) control, respectively. By comparing the sequence admittance characteristics of the GCI under two control strategies, combined with the sequence admittance model and Nyquist criterion, this paper analyzes the influence of voltage feedforward and control parameters on the stability of the GCI under two control strategies. The results show that the stability of GCI under PR control is slightly better than that under PI control. At the same time, the voltage feedforward control does reduce the stability of the GCI system under the two control strategies. Finally, the accuracy of the theoretical analysis is verified by simulation and experiment.
Source: crossref · Quality: baseline
Research context
OpenAlex topics: Microgrid Control and Optimization · Multilevel Inverters and Converters · Advanced DC-DC Converters
SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.
Affiliations
School of Electric Power, North China University of Water Resources and Electric Power, Zhengzhou 450045, China
Funding
North China University of Water Resources and Electric Power
References (26)
Show source-provided references
1. A Distributed Transmission-Distribution-Coupled Static Voltage Stability Assessment Method Considering Distributed Generation10.1109/TPWRS.2017.2762473 ↗
2. A Self-Regulating Virtual Synchronous Generator Control of Doubly Fed Induction Generator-Wind Farms10.1109/ICJECE.2022.3223510 ↗
3. An Enhancing Grid Stiffness Control Strategy of STATCOM/BESS for Damping Sub-Synchronous Resonance in Wind Farm Connected to Weak Grid10.1109/TII.2019.2960863 ↗
4. Systematic Procedure for Mitigating DFIG-SSR Using Phase Imbalance Compensation10.1109/TSTE.2021.3104719 ↗
5. Impact of Short-Circuit Ratio and Phase-Locked-Loop Parameters on the Small-Signal Behavior of a VSC-HVDC Converter10.1109/TPWRD.2014.2330518 ↗
6. Overview of Stability Research for Grid-Connected Inverters Based on Impedance Analysis Method
7. Impedance-Based Stability Criterion for Grid-Connected Inverters10.1109/TPEL.2011.2136439 ↗
8. Unified Impedance Model of Grid-Connected Voltage-Source Converters10.1109/TPEL.2017.2684906 ↗
9. Output Impedance Modeling of Single-Phase Grid-Tied Inverters with Capturing the Frequency-Coupling Effect of PLL10.1109/TPEL.2019.2946984 ↗
10. Impedance Modeling and Stability Analysis of Three-Phase Four-Leg Grid-Connected Inverter Considering Zero-Sequence10.1109/ACCESS.2021.3087331 ↗
11. Sequence Impedance Modeling of Virtual Synchronous Generator Considering Frequency Coupling Effect
12. Couplings in Phase Domain Impedance Modeling of Grid-Connected Converters
13. Frequency Coupling Characteristic Modeling of Grid-connected Inverter and System Stability Analysis
14. Admittance-based stability comparative analysis of grid-connected inverters with direct power control and closed-loop current control10.1109/TIE.2020.3013550 ↗
15. Stability investigation of three-phase grid-tied PV inverter systems using impedance models10.1109/JESTPE.2020.3047964 ↗
16. Manoloiu, A., Pereira, H.A., Teodorescu, R., Bongiorno, M., Eremia, M., and Silva, S.R. (July, January 28). Comparison of PI and PR current controllers applied on two-level VSC-HVDC transmission system. Proceedings of the 2015 IEEE Eindhoven PowerTech, Eindhoven, The Netherlands.10.1109/PTC.2015.7232648 ↗
17. Impedance-Based Analysis of Grid-Synchronization Stability for Three-Phase Paralleled Converters10.1109/TPEL.2015.2419712 ↗
18. Modeling and Control Parameters Design for Grid-Connected Inverter System Considering the Effect of PLL and Grid Impedance10.1109/ACCESS.2019.2950933 ↗
19. Frequency-Coupling Admittance Modeling of Converter-Based Wind Turbine Generators and the Control-Hardware-in-the-Loop Validation10.1109/TEC.2019.2940076 ↗
20. Sequence Impedance Model and Interaction Stability Research of Three-phase Grid-connected Inverters with Considering Coupling Effects
21. Stability enhancement control strategy for grid-connected wind power system based on composite feedforward damping10.1016/j.ijepes.2024.109908 ↗
22. Comparative study of symmetrical controlled grid-connected inverters10.1109/TPEL.2021.3122002 ↗
23. Two causes of the inverter-based grid-connected system instability in weak grids
24. Stability enhancing voltage feed-forward inverter control method to reduce the effects of phase-locked loop and grid impedance10.1109/JESTPE.2020.2987923 ↗
25. High frequency stability analysis and suppression strategy of MMC-HVDC systems (Part I): Stability analysis
26. Stationary frame current regulation of PWM inverters with zero steady-state error10.1109/TPEL.2003.810852 ↗