Long-Lifetime Event-Driven Wireless Monitoring System for Pole-Mounted Transformers
Source abstract
Abstract
As smart grids develop rapidly, low-cost monitoring systems for pole-mounted transformers increase in demand. Even though battery-powered wireless monitoring systems appear to provide optimal solutions, they consume large amounts of energy for continuous sampling and data transmission. Operation and maintenance costs then increase owing to reduced battery lifetime and battery replacement. To overcome this problem, this paper presents an event-driven battery-powered wireless monitoring system that monitors abnormalities of a transformer and transmits data only if an abnormality occurs. When the proposed event controller detects an abnormality, it enables a root mean square (RMS) converter and a peak detector for sampling and transmitting the maximum RMS value of the abnormal signal and then falls into sleep mode until the next event to save energy. Simulation and experimental results show that the proposed system enhances battery lifetime by up to two orders of magnitude compared to a conventional battery-powered wireless monitoring system.
Source: crossref · Quality: baseline
Research context
OpenAlex topics: Power Transformer Diagnostics and Insulation · Islanding Detection in Power Systems · High voltage insulation and dielectric phenomena
SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.
Affiliations
Department of Electronic Engineering, Korea University, Seoul 02841, Korea
References (29)
Show source-provided references
1. Power transformers monitoring based on electrical measurements: State of the art10.1049/iet-gtd.2017.2086 ↗
2. Power transformer protection using an instantaneous-current-value negative sequence differential element10.1016/j.ijepes.2018.12.033 ↗
3. Outage data analysis of utility power transformers based on outage reports during 2002–200910.1016/j.ijepes.2012.10.060 ↗
4. Vahidi, F., and Tenbohlen, S. (2014, January 25–26). Statistical failure analysis of European substation transformers. Proceedings of the Diagnostik elektrischer Betriebsmittel 2014—Beiträge der 6. ETG-Fachtagung, Berlin, Germany.
5. Marks, J., Martin, D., Saha, T., Krause, O., Alibegovic-Memisevic, A., Russell, G., Buckley, G., Chinnarajan, S., Gibson, M., and MacArthur, T. (2016, January 25–28). An analysis of Australian power transformer failure modes, and comparison with international Surveys. Proceedings of the 2016 Australasian Universities Power Engineering Conference (AUPEC), Brisbane, Australia.10.1109/AUPEC.2016.7749314 ↗
6. Investigation into Modeling Australian Power Transformer Failure and Retirement Statistics10.1109/TPWRD.2018.2814588 ↗
7. Dissolved gas analysis evaluation in electric power transformers using conventional methods a review10.1109/TDEI.2017.005959 ↗
8. Bushing failure in power transformers and the influence of moisture with the spectroscopy test10.1016/j.engfailanal.2018.08.006 ↗
9. Detection of power transformer bushing faults and oil degradation using frequency response analysis10.1109/TDEI.2015.005032 ↗
10. Application of neuro-fuzzy scheme to investigate the winding insulation paper deterioration in oil-immersed power transformer10.1016/j.ijepes.2013.04.023 ↗
11. Detection of Power Transformer Winding Deformation Using Improved FRA Based on Binary Morphology and Extreme Point Variation10.1109/TIE.2017.2752135 ↗
12. Evaluation of transformer core contribution to partial discharge electromagnetic waves propagation10.1016/j.ijepes.2016.03.054 ↗
13. Experimental Verification and Electromagnetic-Mechanics-Acoustic Field Coupling Analysis of Transformer Pressure Relief Valve Malfunctions Due to External Short-Circuit Faults
14. Castro, B., Clerice, G., Ramos, C., Andreoli, A., Baptista, F., Campos, F., and Ulson, J. (2016). Partial Discharge Monitoring in Power Transformers Using Low-Cost Piezoelectric Sensors. Sensors, 16.10.3390/s16081266 ↗
15. Infrared detection of transformer insulation degradation due to accelerated thermal aging10.1109/94.671924 ↗
16. New near-infrared absorbance peak for inhibitor content detection in transformer insulating oil10.1016/j.snb.2018.03.064 ↗
17. A real time study on condition monitoring of pole-mounted transformer using thermal imager10.1016/j.infrared.2018.02.009 ↗
18. Predictive Diagnosis of High-Power Transformer Faults by Networking Vibration Measuring Nodes with Integrated Signal Processing10.1109/TIM.2016.2552658 ↗
19. Transformer fault diagnosis method using IoT based monitoring system and ensemble machine learning10.1016/j.future.2020.03.008 ↗
20. Computerized power transformer monitoring based on internet of things10.14419/ijet.v7i4.16280 ↗
21. A new vibration analysis approach for transformer fault prognosis over cloud environment10.1016/j.ijepes.2018.02.026 ↗
22. A smart IoT based system for monitoring and controlling the sub-station equipment10.1016/j.iot.2019.100085 ↗
23. Chang, H., and Lin, C. (2011, January 1–4). Partial discharge detection in lightning surge for pole-mounted equipments using RMS and maximum value of electric charges. Proceedings of the 2011 7th Asia-Pacific International Conference on Lightning, Chengdu, China.10.1109/APL.2011.6111063 ↗
24. Analysis of acoustic emission in chatter vibration with tool wear effect in turning10.1016/S0890-6955(99)00093-0 ↗
25. Capacity and spectrum-aware communication framework for wireless sensor network-based smart grid applications10.1016/j.csi.2017.03.003 ↗
26. Assessment of Macro Fiber Composite Sensors for Measurement of Acoustic Partial Discharge Signals in Power Transformers10.1109/JSEN.2017.2735858 ↗
27. Electric Signature Detection and Analysis for Power Equipment Failure Monitoring in Smart Grid10.1109/TII.2020.3017080 ↗
28. Self-Powered RFID Sensor Tag for Fault Diagnosis and Prognosis of Transformer Winding10.1109/JSEN.2017.2738028 ↗
29. Lee, Y. (2020). Design and Method of Developing Energy Harvester from Daily life Energy Sources for Powering IoT Devices. [Ph.D. Thesis, Sungkyunkwan University].