journal article·2024-02-17Open access

Enhancing Dehumidification in the Cable Room of a Ring Main Unit through CFD-EMAG Coupling Simulation and Experimental Verification

Yaoyu Yan, Futang Xing, Haonan Gao, Dan Mei

Applied Sciences· Volume 14· Issue 4

Abstract

The cable room, located at the base of the ring main unit, is prone to water vapor due to its proximity to damp cable holes and its relatively enclosed structure. This may penetrate internally and ultimately affect operational safety. Therefore, a dehumidifier was introduced to utilize dry air for internal circulation. To enhance the dehumidification in the cable room, the cable room device was designed for experimental research. Meanwhile, computational fluid dynamics (CFD)-electromagnetic (EMAG) coupling simulation is used to calculate the power loss of heat sources and their influence on multiple physical fields in numerical simulations. The feasibility of this study was confirmed by comparing the relative humidity, temperature, and velocity values between the experimental and numerical approaches. Furthermore, the layout of the ventilation pipes was modified to a vertical distribution, with upward supply and downward suction, to improve the airflow. The results indicate that the maximum relative errors in temperature, relative humidity, and velocity are only 3.61%, 7.14%, and 7.14%, respectively, which fall within an acceptable range. On this basis, additional simulation analysis was conducted on the humidity, dew point temperature, and airflow within the cable room, using an optimized model with a more comprehensive internal structure and cables. After implementing an optimized ventilation pipe layout, the relative humidity at the corresponding measuring points can decrease by up to 10.6%. The dew point temperature has decreased by 2.61 °C and the airflow has become more stable.
Source: crossref · Quality: baseline

Research context

OpenAlex topics: Thermal Analysis in Power Transmission · Mechanical stress and fatigue analysis · Power Line Inspection Robots

SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.

Affiliations

Hubei Key Laboratory for Efficient Utilization and Agglomeration of Metallurgic Mineral Resources, Wuhan University of Science and Technology, Wuhan 430081, China

References (19)

Show source-provided references
1. The application of fluorescent optical fiber in partial discharge detection of Ring Main Unit10.1016/j.measurement.2021.108979 ↗
2. Bharat Heavy Electricals Limited (2006). Handbook of Switchgears, McGraw-Hill.
3. Analysis and solution of dewing problems for the looped-network switchgear
4. 110–500 kV analysis of composite insulator flashover on transmission line and countermeasure of China
5. Study and practice of anti-condensation technology for high-voltage switchgear
6. Indoor dewing phenomenon and strategy in metal-enclosed switchgear
7. Simulation environment design for the investigation of damping and dewing mechanisms in the 12 kV high-voltage switchgear10.1051/e3sconf/20185303001 ↗
8. Research of outdoor equipment condensation development process based on improved morphology and optimization of condensation prevention measures
9. Discussion about the heating and dehumidification system in 12 kV switchgear
10. Humidity control of RMU based on COMSOL simulation analysis
11. Coupled numerical modelling of power loss generation in busbar system of low-voltage switchgear10.1016/j.ijthermalsci.2014.04.001 ↗
12. Numerical simulation on condensation phenomenon in the switch cabinet
13. Anti-condensation method for outdoor RMU based on finite element analysis
14. Optimum simulation of thermal field for switchgear
15. Discussion on mechanism of the dampness and dewing inside 12 kV high-voltage switchgear and its key control techniques
16. Optimization on airflow distribution for anti-condensation of high-voltage switchgear using CFD method10.1016/j.csite.2021.101479 ↗
17. Pan, M.L. (2018). Research on Influence Law of Force on the Bushing Affected by Cable Bending in 10 kV RMU. [Master’s Thesis, Three Gorges University].
18. Li, Z.W. (2020). Temperature Field Modeling and Thermal Analysis of Medium Voltage Switchgear Based on ANSYS. [Master’s Thesis, Shanghai University of Engineering Science].
19. Research on Dehumidification Scheme of Cable Treanch in 35 kV Switchgear Room