journal article·2021-05-13Open access

Analysis on the Exhaust Air Recirculation of the Ventilation System in Multi-Story Building

Seonghyun Park, Hyungyu Park, Janghoo Seo

Applied Sciences· Volume 11· Issue 10

Abstract

In South Korea, the installation of a mechanical ventilation system is mandatory for the management of indoor air quality, and various studies concerning the ventilation rate and performance of the ventilation system have been conducted. However, only a few studies have been conducted regarding the recirculation rate of the ventilation system. If the appropriate arrangement of intake and exhaust vents in the ventilation system is not considered, the pollutants emitted from the circulation movement may be recirculated into the indoor environment and cause the degradation of the performance of the ventilation system. Therefore, this study aimed to quantitatively analyze the recirculation rate of pollutants emitted from a kindergarten building with an installed mechanical ventilation system in Seoul, South Korea, using computational fluid dynamics (CFD) analysis, and analyze the effectiveness of the guide panel installed for the prevention of the pollutants’ recirculation. The number of cases for the CFD analysis was set to a total of ten based on the ventilation rate in a mechanical ventilation system, external wind direction, and the existence of the guide panel for preventing the recirculation of exhaust air. The maximum recirculation rate of exhaust air without the installation of a guide panel was shown to be 20.0%. The maximum recirculation rate in the case where the external wind speed, direction of wind, and the ventilation rate were assumed to be identical to the other case but the guide panel for preventing the recirculation of exhaust air was assumed to be installed was 7.7%, 12.3% lower compared with the case with maximum recirculation rate.
Source: crossref · Quality: baseline

Research context

OpenAlex topics: Wind and Air Flow Studies · Building Energy and Comfort Optimization · Infection Control and Ventilation

SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.

Affiliations

Department of Industry-Academic Cooperation Foundation, Kookmin University, 77 Jeongneung-ro, Seongbuk-gu, Seoul 02707, Korea

Department of Architecture, Graduated School, Kookmin University, 77 Jeongneung-ro, Seongbuk-gu, Seoul 02707, Korea

School of Architecture, Kookmin University, 77 Jeongneung-ro, Seongbuk-gu, Seoul 02707, Korea

References (27)

Show source-provided references
1. Health effects of particulate air pollutioin10.1016/j.annepidem.2009.01.018 ↗
2. Global dispersion of bacterial cells on Asian dust10.1038/srep00525 ↗
3. Renewable and sustainable energy saving strategies for greenhouse systems: A comprehensive review10.1016/j.rser.2016.05.077 ↗
4. (2021, March 13). National Law Information Center, Law and Administration Regulations for Guidelines and Suggestions on Facilities for Buildings in Korea. Available online: http://www.law.go.kr.
5. Experimental study of ventilation performance in laboratories with chemical spills10.1016/j.buildenv.2012.04.022 ↗
6. Particulate concentrations within a reduced-scale room operated at various air exchange rates10.1016/j.buildenv.2013.03.023 ↗
7. Optimization of dilution ventilation layout design in confined environments using Computational Fluid Dynamics (CFD)10.1016/j.jlp.2019.05.002 ↗
8. Kravchenko, I., Kosonen, R., and Kilpeläinen, S. (2021). Performance Analysis of the Demand-Based Ventilation in a Nordic Apartment Building. Appl. Sci., 11.10.3390/app11010176 ↗
9. Experimental analysis of indoor air quality improvement achieved by using a Clean-Air Heat Pump (CAHP) air-cleaner in a ventilation system10.1016/j.buildenv.2017.06.032 ↗
10. Performance of ventilation in Estonian apartment buildings10.1016/j.egypro.2017.09.681 ↗
11. Consequence analysis of accidental release of supercritical carbon dioxide from high pressure pipelines10.1016/j.ijggc.2016.10.010 ↗
12. Optimization of water mist droplet size by using CFD modeling for fire suppressions10.1016/j.jlp.2016.04.010 ↗
13. Cen, K., Song, B., Shen, R., Zhang, Y., Yu, W., and Wang, Q. (2019). Dynamic characteristics of gas explosion and its mitigation measures inside residential buildings. Math. Probl. Eng.10.1155/2019/2068958 ↗
14. Simulation of heavy gas dispersion in a large indoor space using CFD model10.1016/j.jlp.2017.01.012 ↗
15. A review of the performance of different ventilation and airflow distribution systems in buildings10.1016/j.buildenv.2013.12.009 ↗
16. Advances in building simulation and computational techniques: A review between 1987 and 201410.1016/j.enbuild.2016.06.080 ↗
17. CFD simulation of outdoor ventilation of generic urban configurations with different urban densities and equal and unequal street widths10.1016/j.buildenv.2015.04.018 ↗
18. A Study on Analysis of Recirculation Rate of Pollutant (CO2) in the Ventilation System of Apartment Houses by CFD Simulation
19. CFD and wind-tunnel analysis of outdoor ventilation in a real compact heterogeneous urban area: Evaluation using “air delay”10.1016/j.buildenv.2017.10.013 ↗
20. ANSYS, Ltd (2019). ANSYS Academic Research Fluent, Release 19.2, Help System, Theory Guide, Ansys Inc.
21. CFD simulations of wind distribution in an urban community with a full-scale geometrical model10.1016/j.buildenv.2017.02.021 ↗
22. Influence of surrounding buildings on wind flow around a building predicted by CFD simulations10.1016/j.buildenv.2018.05.011 ↗
23. Park, S., and Seo, J. (2016). Optimum installation of sorptive building materials using contribution ratio of pollution source for improvement of indoor air quality. Int. J. Environ. Res. Public Health, 13.10.3390/ijerph13040396 ↗
24. Zender-Świercz, E. (2021). Review of IAQ in Premises Equipped with Façade–Ventilation Systems. Atmosphere, 12.10.3390/atmos12020220 ↗
25. Assessing methods to extrapolate the vertical wind-speed profile from surface observations in a city centre during strong winds10.1016/j.jweia.2017.09.007 ↗
26. Effect of diurnal variation in wind velocity profiles on ventilation performance estimates10.1016/j.enbuild.2016.08.075 ↗
27. AIK (2021, May 13). Korean Building Code. 2016, Architectural Institute of Korea. c2016. Available online: https://www.law.go.kr/LSW//flDownload.do?flSeq=83070997.