Characterization of Lithium-Ion Battery Fire Emissions—Part 3: Gas Emissions
Source abstract
Abstract
Lithium-ion batteries (LIBs) release significant amounts of toxic, corrosive, and flammable gases when they enter thermal runaway (TR). These emissions can be hazardous to human health, damage nearby equipment, pose fire and explosion risks, and degrade air quality. This study measured concentrations for a range of hazardous gases released from TR-driven combustion of cylindrical lithium iron phosphate (LFP) and pouch-style lithium cobalt oxide (LCO) LIB cells. Gas emissions were measured by dedicated analyzers and Fourier transform infrared spectroscopic (FTIR) analysis, and emission factors were calculated. Dangerous concentrations of hydrogen fluoride (HF) were observed, reaching up to 50 ppm from the combustion of single LIB cells. Large amounts of combustible electrolyte solvents and light hydrocarbons were released in some cases, depending on cell combustion behavior. Electrolyte solvents, hydrogen chloride (HCl), and particles were released earlier than other species and should be targeted for early TR detection. Gas emissions were correlated with cell state of charge (SOC) and combustion behavior. Cells at high SOCs had higher peak concentrations of HF, HCl, CO, and flammable hydrocarbons, and these peaks happened sooner after cell failure than for low-SOC tests.
Source: crossref · Quality: baseline
Research context
OpenAlex topics: Advanced Battery Technologies Research · Fire dynamics and safety research · Combustion and Detonation Processes
SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.
Affiliations
Division of Atmospheric Sciences, Desert Research Institute, Reno, NV 89512, USA
Department of Mechanical Engineering, University of Nevada, Reno, NV 89557, USA
Division of Hydrologic Sciences, Desert Research Institute, Reno, NV 89512, USA
Funding
National Aeronautics and Space Administration · U.S. National Science Foundation
References (25)
Show source-provided references
1. Review of gas emissions from lithium-ion battery thermal runaway failure—Considering toxic and flammable compounds10.1016/j.est.2024.111288 ↗
2. Nilsson, E.J.K., and Ahlberg Tidblad, A. (2024). Gas Emissions from Lithium-Ion Batteries: A Review of Experimental Results and Methodologies. Batteries, 10.10.3390/batteries10120443 ↗
3. Nedjalkov, A., Meyer, J., Köhring, M., Doering, A., Angelmahr, M., Dahle, S., Sander, A., Fischer, A., and Schade, W. (2016). Toxic Gas Emissions from Damaged Lithium Ion Batteries—Analysis and Safety Enhancement Solution. Batteries, 2.10.3390/batteries2010005 ↗
4. Amano, K.O., Hahn, S.-K., Butt, N., Vorwerk, P., Gimadieva, E., Tschirschwitz, R., Rappsilber, T., and Krause, U. (2023). Composition and Explosibility of Gas Emissions from Lithium-Ion Batteries Undergoing Thermal Runaway. Batteries, 9.10.3390/batteries9060300 ↗
5. Toxic fluoride gas emissions from lithium-ion battery fires10.1038/s41598-017-09784-z ↗
6. Meta-analysis of heat release and smoke gas emission during thermal runaway of lithium-ion batteries10.1016/j.est.2022.106579 ↗
7. Claassen, M., Bingham, B., Chow, J.C., Watson, J.G., Wang, Y., and Wang, X.L. (2024). Characterization of Lithium-ion Battery Fire Emissions—Part 1: Chemical Composition of Fine Particles (PM2.5). Batteries, 10.10.3390/batteries10090301 ↗
8. Claassen, M., Bingham, B., Chow, J.C., Watson, J.G., Wang, Y., and Wang, X.L. (2024). Characterization of Lithium-ion Battery Fire Emissions—Part 2: Particle Size Distributions and Emission Factors. Batteries, 10.10.3390/batteries10100366 ↗
9. AA Portable Power Corp (2026). Model 544792 Polymer Lithium-Ion Battery Product Specification, AA Portable Power Corp.. Available online: https://www.batteryspace.com/prod-specs/3175.pdf.
10. (2026). APR18650m1B Power Cells Nanophosphate® Technology Data Sheet, LithiumWerks. Available online: https://lithiumwerks.com/products/lithium-ion-18650-cells/.
11. A biomass combustion chamber: Design, evaluation, and a case study of wheat straw combustion emission tests10.4209/aaqr.2015.03.0167 ↗
12. Characterization of gas and particle emissions from open burning of household solid waste from South Africa10.5194/acp-23-8921-2023 ↗
13. NIOSH (2007). NIOSH Pocket Guide to Chemical Hazards.
14. OSHA (2023, October 01). 29 CFR 1910.1000. Occupational Safety and Health Standards-Toxic and Hazardous Substances-Air Contaminants, Available online: https://www.osha.gov/pls/oshaweb/owadisp.show_document?p_table=STANDARDS&p_id=9991.
15. U.S. EPA (2025, December 04). About Acute Exposure Guideline Levels (AEGLs), Available online: https://www.epa.gov/aegl/about-acute-exposure-guideline-levels-aegls.
16. AIHA (2025). ERPGs (Emergency Response Planning Guidelines™), The American Industrial Hygiene Association (AIHA). Available online: https://www.aiha.org/get-involved/aiha-guideline-foundation/erpgs.
17. Zabetakis, M.G. (1965). Flammability Characteristics of Combustible Gases and Vapors.10.2172/7328370 ↗
18. Explosion hazards from lithium-ion battery vent gas10.1016/j.jpowsour.2019.227257 ↗
19. Lithium-ion battery electrolyte emissions analyzed by coupled thermogravimetric/Fourier-transform infrared spectroscopy10.1016/j.jpowsour.2017.08.082 ↗
20. Gas generation measurement and evaluation during mechanical processing and thermal treatment of spent Li-ion batteries10.1016/j.wasman.2018.11.029 ↗
21. Zhou, Z., Liu, Y., Jiang, H., Bai, Z., Sun, L., Liu, J., and Zhao, W. (2024). The effects of ambient temperature and atmospheric humidity on the diffusion dynamics of hydrogen fluoride gas leakage based on the computational fluid dynamics method. Toxics, 12.10.3390/toxics12030184 ↗
22. Scenario-based prediction of Li-ion batteries fire-induced toxicity10.1016/j.jpowsour.2016.02.090 ↗
23. Andersson, P., Blomqvist, P., Loren, A., and Larsson, F. (2013). Investigation of Fire Emissions from Li-Ion Batteries, SP Technical Research Institute of Sweden. Available online: https://www.diva-portal.org/smash/get/diva2:962743/FULLTEXT01.pdf.
24. Gully, B., Helgesen, H., Skogtvedt, J., and Kostopoulos, D. (2019). Technical Reference for Li-Ion Battery Explosion Risk and Fire Suppression, DNV GL AS Maritime, Partner Group. [4th ed.]. Available online: https://www.dnv.com/Publications/technical-reference-for-li-ion-battery-explosion-risk-and-fire-suppression-165062.
25. Thermal runaway and fire behaviors of lithium iron phosphate battery induced by over heating10.1016/j.est.2020.101714 ↗